WIKA DPT-10 User Manual

Page 51

Advertising
background image

Part sum counter

0

.0000 10

00

gal

Modify settings?

2

Activate the function "Modify settings?" with [OK].

Part sum counter

Effective pressure transmitter

Unit

3

Confirm with [OK] "Effective pressure transmitter".

Part sum counter

Mass flow

Volume flow

Without unit

4

Select the requested variable with [->] and confirm with [OK].

5

Select calibration unit of the effective pressure transmitter with [-
>

]

, for example m

3

/s and confirm with [OK].

Part sum counter

0 % = +0000

m

3

/s=

100 % = +0000

m

3

/s=

6

Edit with [OK] and set the requested values with [+] and [->].

7

Confirm with [OK] and jump back to the indication of the part sum
counter.

8

Select with [->] the unit of the sum counter, adjust the requested
unit with [->], for example m

3

/s and confirm with [OK].

The setting of the part sum counter is hence terminated, the counting
function is activated.

The procedure of the total sum counter is the same.

This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the indicating
and adjustment module. A description of the function is available in the
operating instructions manual "Indicating and adjustment module".

The following data are read out or written with this function:

l

Measured value presentation

l

Application

l

Unit of measurement

l

Adjustment

l

Damping

Copy sensor data

Differential pressure transmitter DPT10 - metal measuring diaphragm • Foundation Fieldbus

51

6 Adjustment with the indicating and adjustment module

37246

-

EN

-100120