(0.0015 % x TD + 0.053) of the set span +

influence of the isolating diaphragm

Influence of the product or ambient temperature

Applies to instruments in basic version with digital signal output (HART, Profibus PA, Foundation
Fieldbus) as well as to instruments with analogue current output 4 … 20 mA. Specifications refer
to the set span. Turn down (TD) = nominal measuring range/set span.

Temperature range

Measuring range

Thermal changes of the zero
signal and the output span relat-
ing to the adjusted span

-10 … +60 °C (+14 … +140 °F)

10 mbar, 30 mbar

±

(0.31 x TD + 0.06) %

100 mbar

±

(0.18 x TD + 0.02) %

500 mbar, 3 bar

±

(0.08 x TD + 0.05) %

16 bar

±

(0.1 x TD + 0.1) %

16 bar

±

(0.08 x TD + 0.05) %

-40 … +10 °C (-40 … +50 °F)

+

60 … +85 °C (+140 … +185 °F)

10 mbar, 30 mbar

±

(0.45 x TD + 0.1) %

100 mbar

±

(0.3 x TD + 0.15) %

500 mbar, 3 bar

±

(0.12 x TD + 0.1) %

16 bar

±

(0.15 x TD + 0.2) %

40 bar

±

(0.37 x TD + 0.1) %

Applies also to instruments with analogue 4 … 20 mA current output and refers to the set span.

Thermal change, current output

<

0.15 % at -40 … +80 °C (-40 … +176 °F)

Influence of the system pressure on the zero point and span

316L

, Alloy C276-, Alloy C276 gold-rhodium coated diaphragm

Measuring cell

10

mbar

30

mbar

100

mbar

500

mbar

Influence of the sys-
tem pressure to the
zero point

±

0.15 % of URL/

7 bar

±

0.35 % of URL/

70 bar

±

0.15 % of URL/

70 bar

±

0.075 % of URL/

70 bar

Influence of the sys-
tem pressure to the
span

±

0.035 % of URL/

7 bar

±

0.14 % of URL/

70 bar

±

0.14 % of URL/

70 bar

±

0.14 % of URL/

70 bar

Measuring cell

3

bar

16

bar

40

bar

Influence of the system
pressure to the zero point

±

0.075 % of URL/7 bar

±

0.075 % of URL/70 bar

±

0.075 % of URL/70 bar

Differential pressure transmitter DPT10 - metal measuring diaphragm • Foundation Fieldbus