WIKA DPT-10 User Manual

Page 74

Advertising
background image

Characteristics

linear

Position of the measuring cell

constant, in the range: horizontal ±1°

Span

based on the zero point

Diaphragm material

316L, Alloy C276, gold rhodium plated, Monel

Filling oil

Silicone oil

Material, lateral flanges

316L

Influence of the installation position basic
version

4 mbar

9)10)

A position-dependent zero-point shift can be corrected (see also chapter "General installation
instructions
" and "Installation instructions, isolating diaphragm systems").

Deviation determined according to the limit point method according to IEC 60770

11

)

Applies to digital interfaces (HART, Profibus PA, Foundation Fieldbus) as well as to analogue
current output 4 … 20 mA. Specifications refer to the set span. Turn down (TD) is the ratio nominal
measuring range/set span.

Reference accuracy - all versions

The following applies to square root extracted characteristics: The accuracy data of DPT10 are
entered with factor 0.5 in the accuracy calculation of the flow.

Reference accuracy - Basic version

10 mbar, 30 mbar measuring cell

-

Turn down 1 : 1

±

0.15 % of the set span

-

Turn down > 1 : 1

±

0.15 % of the set span x TD

100 mbar measuring cell

-

Turn down 1 : 1 up to 4 : 1

±

0.075 % (±0.05 %) of the set span

-

Turn down > 4 : 1

±

(0,012 % x TD + 0.027) of the set span

Measuring cells ≥ 500 mbar

-

Turn down 1 : 1 up to 15 : 1

±

0.075 % (±0.05 %) of the set span

-

Turn down > 15 : 1

±

(0.0015 % x TD + 0.053) of the set span

Reference accuracy - Isolating diaphragm versions

100 mbar measuring cell

-

Turn down 1 : 1 up to 4 : 1

±

0.075 % (±0.05 %) of the set span + influence of

the isolating diaphragm

-

Turn down > 4 : 1

±

(0.012 % x TD + 0.027) of the set span + influence

of isolating diaphragm

Measuring cells ≥ 500 mbar

-

Turn down 1 : 1 up to 15 : 1

±

0.075 % (±0.05 %) of the set span + influence of

the isolating diaphragm

-

Turn down > 15 : 1

9)

Instrument is rotated vertically to the diaphragm axis.

10)

For instruments with inert oil, the value doubles.

11)

Incl. non-linearity, hysteresis and non-repeatability.

74

Differential pressure transmitter DPT10 - metal measuring diaphragm • Foundation Fieldbus

11 Supplement

37246

-EN

-100120