WIKA DPT-10 User Manual

Page 84

Advertising
background image

-

Result of table plausibility check

-

"

0: ""Uninitialized"" 1: ""Good"" 2: ""Not monotonous increasing"" 3: ""Not monotonous

decreasing"" 4: ""Not enough values transmitted"" 5: ""Too many values transmitted"" 6:
""G

radient of edge too high"" 7: ""Values not excepted"" 8: ""Table currently loaded"" 9: ""Sorting

and checking table"""

l

SUB_DEVICE_NUMBER

l

SENSOR_ELEMENT_TYPE

-

0: "non-specific"

l

display_source_selector

-

Selects the type of value that is displayed on the indication-/adjustement-module

-

"

0: ""Physical value"" 1: ""Percent value"" 2: ""Lin percent value"" 6: ""Out(AI1)"" 7: ""Level"" 8:

""O

ut(AI2)"" 9: ""Out(AI3)"""

l

max_peak_sensor_value

-

Holds the maximum sensor value. Write access resets to current value. Unit derives from
'S

ensor_range.unit'

-

Write access resets to current value

l

min_peak_sensor_value

-

Holds the minimum sensor value. Write access resets to current value. Unit derives from
'S

ensor_range.unit'

-

Write access resets to current value

l

CAL_POINT_HI

-

Highest calibrated value. For calibration of the high limit point you give the high measurement
value (pressure) to the sensor and transfer this point as HIGH to the transmitter. Unit derives from
'S

ensor_range.unit'

l

CAL_POINT_LO

-

Lowest calibrated value. For calibration of the low limit point you give the low measurement value
(pressure) to the sensor and transfer this point as LOW to the transmitter. Unit derives from
'S

ensor_range.unit'

l

CAL_MIN_SPAN

-

Minimum calibration span value allowed. Necessary to ensure that when calibration is done, the
two calibrated points (high and low) are not too close together. Unit derives from 'Sensor_range.
unit'

l

SCALE_IN

-

Min/max-adjustment: Upper and lower calibrated points of the sensor. Unit derives from
'S

ensor_range.unit'

l

trimmed_value

-

Sensor value after the trim processing. Unit derives from 'Sensor_range.unit'

l

sensor_sn

-

Sensor serial number

l

temperature

-

Process temperature. Selected as input to AIFB by setting 'Channel' = 4. Unit derives from
'T

emperature.unit'

l

temperature_unit

-

Unit code of 'Temperature', 'Max/Min_peak_temperature_value'

-

°C

, °F, K, °R

84

Differential pressure transmitter DPT10 - metal measuring diaphragm • Foundation Fieldbus