WIKA DPT-10 User Manual

Page 73

Advertising
background image

Version, nominal measuring range

Dead time t

1

Time constant t

2

Isolating diaphragm version, all nominal measuring
ranges

Depending on the isolat-
ing diaphragm

Depending on the isolating
diaphragm

Response time with Foundation Fieldbus

-

cyclically approx.

10 ms

-

acyclically approx.

50 ms

Damping (63 % of the input variable)

0 … 999 s, adjustable

Additional output parameter - temperature

Processing is made via output signal HART multidrop, Profibus PA and Foundation Fieldbus

Range

-50 … +150 °C (-58 … +302 °F)

Resolution

1 °C (1.8 °F)

Accuracy in the range of 0 … +100 °C
(+32 … +212 °F)

±

3 K

Accuracy in the range of -50 … 0 °C
(-58 … +32 °F) and +100 … +150 °C
(+212 … +302 °F)

typ. ±3 K

Input variable

Measured variable

Differential pressure, flow and level derived from it

Nominal range

Lower measurement
limit

Upper measuring limit

Smallest adjustable
span

10 mbar (1 kPa)

-10 mbar (-1 kPa)

+

10 mbar (+1 kPa)

0.25 mbar (25 Pa)

30 mbar (3 kPa)

-30 mbar (-3 kPa)

+

30 mbar (+3 kPa)

0.3 mbar (30 Pa)

100 mbar (10 kPa)

-100 mbar (-10 kPa)

+

100 mbar (+10 kPa)

1 mbar (100 Pa)

500 mbar (50 kPa)

-500 mbar (-50 kPa)

+

500 mbar (+50 kPa)

5 mbar (500 Pa)

3 bar (300 kPa)

-3 bar (-300 kPa)

+

3 bar (+300 kPa)

30 mbar (3 kPa)

16 bar (1600 kPa)

-16 bar (-1600 kPa)

+

16 bar (+1600 kPa)

160 mbar (16 kPa)

40 bar (4000 kPa)

-40 bar (-4000 kPa)

+

40 bar (+4000 kPa)

400 mbar (40 kPa)

Reference conditions and actuating variables (similar to DIN EN 60770-1)

Reference conditions according to DIN EN 61298-1

-

Temperature

+

18 … +30 °C (+64 … +86 °F)

-

Relative humidity

45 … 75 %

-

Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Determination of characteristics

Limit point adjustment according to IEC 61298-2

Differential pressure transmitter DPT10 - metal measuring diaphragm • Foundation Fieldbus

73

11 Supplement

37246

-

EN

-100120

Advertising