WIKA DPT-10 User Manual

Page 80

Advertising
background image

-

Colour - standard PE

Black

-

Colour - standard PUR

Blue

-

Colour - Ex-version

Blue

Electromechanical data - version IP 66/IP 68 with external electronics

Connection cable between IP 68 instrument and external housing:

-

Configuration

Four wires, screen braiding, inner cover, screen
braiding, outer cover

-

Wire cross-section

0.5 mm² (AWG 20)

-

Standard length

5 m (16.40 ft)

-

Max. length

25 m (82.02 ft)

-

Min. bending radius at 25 °C/77 °F

25 mm (0.985 in)

-

Diameter approx.

8 mm (0.315 in)

-

Colour

Blue

Cable entry/plug

23)

-

External housing

l

2 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm),
1 x blind stopper M20 x 1.5

or:

l

1 x cable gland M20 x 1.5, 1 x plug (depending
on version), 1 x blind stopper M20 x 1.5

Spring-loaded terminals for wire cross-sec-
tion up to

2.5 mm² (AWG 14)

Indicating and adjustment module

Voltage supply and data transmission

through the sensor

Indication

LC display in dot matrix

Adjustment elements

4 keys

Protection rating

-

unassembled

IP

20

-

mounted into the sensor without cover

IP

40

Materials

-

Housing

ABS

-

Inspection window

Polyester foil

Voltage supply

Operating voltage

-

Non-Ex instrument

9 … 32 V DC

-

EEx-ia instrument

9 … 24 V DC

-

EEx-d instrument

9 … 32 V DC

23)

Depending on the version M12 x 1, according to DIN 43650, Harting, 7/
8" FF.

80

Differential pressure transmitter DPT10 - metal measuring diaphragm • Foundation Fieldbus

11 Supplement

37246

-EN

-100120

Advertising