WIKA DPT-10 User Manual

Page 83

Advertising
background image

l

primary_value

-

Process Value after min/max-adjustment and linearization. Selected as input to AIFB by setting
'C

hannel' = 1. Unit derives from 'Primary_value_unit'

l

primary_value_unit

-

Unit code of 'Primary_value'

-

%

l

secondary_value_1

-

Process pressure. Selected as input to AIFB by setting 'Channel' = 2. Unit derives from
'S

econdary_value_1_unit'

l

secondary_value_1_unit

-

Unit code of 'Secondary_value_1'

-

bar, PSI, …, m, ft, …; in case of length type engineering unit and access to parameters the
corresponding values will be converted by density factor

l

secondary_value_2

-

Value after min/max-adjustment. Selected as input to AIFB by setting 'Channel' = 3. Unit derives
from 'Secondary_value_2_unit'

l

secondary_value_2_unit

-

Selected unit code for "secondary_value_2"

l

sensor_value

-

Raw sensor value, i.e. the uncalibrated measurement value from the sensor. Unit derives from
'S

ensor_range.unit'

l

sensor_range

-

"S

ensor_range.unit' refers to 'Sensor_value', 'Max/Min_peak_sensor_value', 'Cal_point_hi/lo'

-

includes sensor unit: bar, PSI …; only unit part of DS-68 is writable

l

simulate_primary_value

l

simulate_secondary_value_1

l

simulate_secondary_value_2

l

device status

-

"

0: ""OK"" 13: ""non-specific error"" 17: ""Cal span too small"" 34: ""EEPROM memory fault"" 36:

""ROM

memory fault"" 37: ""RAM memory fault"" 40: ""non-specific hardware fault"" 41: ""Sensor

element not found"" 42: ""No leaking pulse"" 43: ""No trigger signal"" 44: ""EMI error"" 113:
""C

ommunication hardware fault"""

l

linearization type

-

Possible types of linearization are: linear, user defined, cylindrical lying container, spherical
container

-

"

0: ""Linear"" 1: ""User def"" 20: ""Cylindrical lying container"" 21: ""Spherical container"""

l

curve_points_1_10

-

X and Y values for the user defined linearization curve

l

curve_points_11_20

-

X and Y values for the user defined linearization curve

l

curve_points_21_30

-

X and Y values for the user defined linearization curve

l

curve_points_31_33

-

X and Y values for the user defined linearization curve

l

curve status

Differential pressure transmitter DPT10 - metal measuring diaphragm • Foundation Fieldbus

83

11 Supplement

37246

-

EN

-100120