Danger, Warning – Howard HI-102 Overhead Transformer User Manual

Page 12

Advertising
background image

Document 2.4.95, Revision 0

May. 2013

12

Fluid-Filled Overhead Distribution Transformers

voltage switch is in the parallel position. Before

removing the cover or handhole cover, refer to

“Opening the Transformer Tank” for instructions.

5. Grounding—Check to ensure that the trans-

former tank is securely and effectively grounded.

The transformer tank ground pad or nut is

located on the tank.

6. Bolted Connections—Check all bolted connec-

tions for tightness, referring to nominal torque

guidelines contained in Tables 1 through 4.

7. Fluid Level—Check to make sure the fluid level

is correct as indicated by the fluid level gauge

or sight plug, if provided. Be aware that fluid

temperature and orientation of the transformer

tank will cause the fluid level to vary. Transform-

ers are filled to a level that corresponds to a fluid

temperature of 25°C. The actual fluid level will

increase with increasing temperature. The fluid

level indication will also vary when the transform-

ers is not installed in a level orientation.

8. Fluid Temperature—Observe the fluid tempera-

ture gauge and make sure the temperature is

no lower than indicated below before the unit is

energized.

-20°C (-4°F) for conventional transformer oil

and silicone fluid

0°C (32°F) for R-Temp fluid

-10°C (14°F) for FR3™ fluid

9. Internal Fault Detector—If the transformer is

provided with an Internal Fault Detector (IFD),

remove the orange shipping lock after the trans-

former is installed and before it is placed into

service.

10. Current Transformers—If current transform-

ers (CT’s) are present, connect CT leads to the

metering load. If CT leads are not connected to

a metering load, they must be shorted together

and grounded before the transformer is ener-

gized.

11. Accessory Wiring—Check wiring of control and

alarm circuits, if provided, to make sure there

are no loose connections and no damage to wire

insulation.

12. Tank Finish—Check all painted surfaces to make

sure that there is no damage or corrosion.

13. Internal Inspection—Transformer tanks are

sealed at the factory and should not be opened

unless necessary. If the transformer tank must be

accessed, refer to “Opening the Transformer Tank”

for instructions.

Post-Energization Inspection and Tests

After the transformer is energized, the following tests

and inspections should be performed.

!

DANGER

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW WILL RESULT IN DEATH OR SERIOUS

PERSONAL INJURY, AND COULD ALSO RESULT

IN DAMAGE TO THE EQUIPMENT

.

Be aware of dangerous voltages within the

terminal compartment and avoid personal

contact with live terminals.

!

WARNING

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW COULD RESULT IN DEATH OR SERIOUS

PERSONAL INJURY, AND COULD ALSO RESULT

IN DAMAGE TO THE EQUIPMENT.
• Energize the transformer from a remote

location.

• Only qualified personnel with appropriate

equipment should measure transformer

voltages.

• Wear personal protective equipment (PPE)

to prevent injury from potential arc-flash or

contact with dangerous voltages.

• Make sure the transformer is securely and

effectively grounded at all times.

• Current transformer (CT) leads must be

connected to a metering load or shorted

together and grounded to prevent dangerous

voltage at the CT terminals.

1. Verifying Correct Voltage

—Before supplying

voltage from the transformer to the load, verify

that the secondary voltages are correct. Using a

suitable AC voltmeter, measure the voltage of the

secondary windings and make sure they agree

with the secondary voltages listed on the trans-

former nameplate.

Advertising