Document 2.4.95, Revision 0

May. 2013

14

Fluid-Filled Overhead Distribution Transformers

The following operating instructions and descriptions

of switching and fusing devices are intended to be

a general guide for operation of Howard Industries

fluid-filled overhead distribution transformers in

normal environments. Although every effort has been

made to ensure accuracy and completeness, these

instructions and descriptions do not address every

conceivable application or circumstance that might

be encountered. Personnel should read and comply

with any safety and instructional labels that accom-

pany an accessory device.

Some of the accessory devices described below are

optional and may not be present in any particular

transformer design. The inclusion of particular acces-

sory devices in any transformer design is governed

by industry standards and by individual customer

specifications.

!

WARNING

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW COULD RESULT IN DEATH OR SERIOUS

PERSONAL INJURY, AND COULD ALSO RESULT

IN DAMAGE TO THE EQUIPMENT.

• Use a live-line tool (hot stick or shotgun stick)

to operate devices designed to be operated

by a live-line tool.

• Before servicing the transformer, always

de-energize the transformer from a remote

location and then proceed to ground all

primary and secondary transformer terminals

following industry-accepted safe grounding

practices. Grounding secondary terminals

protects against situations such as a standby

generator energizing transformer from the

secondary circuit.

• Follow industry-accepted safety practices.

Utilize personal protective equipment (PPE)

when working with this equipment.

• Do not operate fluid-immersed switching

devices when the insulating fluid temperature

is below the following limits:

-20°C (-4°F) for conventional transformer

oil and silicone fluid

0°C (32°F) for R-Temp fluid

-10°C (14°F) for FR3

fluid

Hot-Stick Operable Devices

Some devices such as low-voltage circuit breakers,

tap switches, multiple-voltage switches and automat-

ic pressure relief devices are designed to be oper-

ated with a live-line tool (hot stick or shotgun stick).

Do not attempt to operate by hand any device that is

designed to be operated with a live-line tool. Inspect,

test and operate the live-line tool according to the in-

structions provided by the live-line tool manufacturer.

Taps and Multiple-Voltage Windings

Transformers with low-voltage ratings of 600 Volts or

less can be provided with either high-voltage taps or

SECTION 5: OPERATION OF SWITCHING AND PROTECTIVE DEVICES