Warning – Howard HI-102 Overhead Transformer User Manual

Page 20

Advertising
background image

Document 2.4.95, Revision 0

May. 2013

20

Fluid-Filled Overhead Distribution Transformers

Drain Valve and Sampling Device

The drain valve and sampling device permit draining

the transformer fluid and sampling the fluid for

testing purposes. The valve is located near the

bottom of the transformer tank. Refer to “Sampling

and Testing the Fluid” and “Draining and Filling the

Tank” for the fluid sampling and draining procedures.

Automatic Pressure Relief Valve

The automatic pressure relief valve (PRV) is

designed to relieve excessive tank pressure that

might occur during operation of the transformer.

The valve consists of a self-resealing, spring-loaded

diaphragm. Some PRV types may include a re-

settable visual flag to indicate that the valve has

operated.

When pressure in the tank exceeds the PRV’s

specified limit, the pressure will cause the valve

to open, venting the excess pressure. After the

internal pressure decreases below the PRV reseal

rating, the valve will automatically close and reseal

the transformer. For PRV’s equipped with a visual

indicating flag, the flag must be manually reset.

!

WARNING

FAILURE TO FOLLOW THE INSTRUCTIONS BE-

LOW COULD RESULT IN MINOR OR MODERATE

PERSONAL INJURY, AND COULD ALSO RESULT

IN DAMAGE TO THE EQUIPMENT.
The cause of PRV activation should always be

investigated, since pressure venting may indicate

a potential problem inside the transformer.

Internal Fault Detector

The Internal Fault Detector (IFD) is a mechanical

sensor that activates when sudden pressure from an

internal arcing fault occurs inside the transformer.

If an internal fault occurs, the IFD releases a visible,

non-resettable orange signal flag. This signal flag

alerts crews that the transformer is faulted and

should not be re-energized. Be aware that the IFD

provides only a visual indication that a fault has

occurred. It is not an electrical disconnect device.

!

WARNING

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW COULD RESULT IN DEATH OR SERIOUS

PERSONAL INJURY, AND COULD ALSO RESULT

IN DAMAGE TO THE EQUIPMENT.
• Do not re-energize a transformer if the IFD

has operated.

• Do not attempt to reset the orange signal

flag.

• Always assume that a transformer might be

faulted, even if the IFD has not operated.

• Never rely solely on the IFD as an indicator of

transformer condition.

• The IFD is a visual indicator only, and should

not be relied on as an electrical disconnect

device.

The IFD also includes a standard pressure relief

valve that is integrated into the sensor to relieve

excessive tank pressures that might occur during

normal operation of the transformer. Refer to

information elsewhere in these instructions

regarding operation of an automatic pressure relief

valve.

The IFD incorporates a removable shipping lock

for use during transportation and storage. The

shipping lock must be removed after the transformer

is installed. Re-install the shipping lock if the

transformer must be relocated. Always transport

IFD-equipped transformers with the shipping lock

installed to prevent accidental operation.

Bushings and Terminals

Tin-plated eye-bolt or spade terminals are provided

as specified by IEEE standards and are suitable for

connection to either aluminum or copper conductors.

High-voltage and low-voltage connections should be

made as indicated on the transformer nameplate.

Clean and properly tighten all terminal connections

to ensure a low-resistance connection and prevent

overheating. Refer to torque guidelines contained

in Table 3. Ensure that there is sufficient electrical

clearance between all live parts, including both

phase-to-phase and phase-to-ground clearances.

Advertising