Warning – Howard HI-102 Overhead Transformer User Manual

Page 16

Advertising
background image

Document 2.4.95, Revision 0

May. 2013

16

Fluid-Filled Overhead Distribution Transformers

Replacement fuses should have the proper rating

and operating characteristics. Refer to the circuit

diagram on the transformer nameplate for the loca-

tion of fuses.

!

WARNING

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW COULD RESULT IN DEATH OR SERIOUS

PERSONAL INJURY, AND COULD ALSO RESULT

IN DAMAGE TO THE EQUIPMENT.
• Do not replace a blown fuse unless the cause

of the fuse operation has been identified and

corrected.

• De-energize the transformer and ground all

terminals before replacing fuses.

• Only qualified personnel with appropriate

measurement devices should measure the

voltages on the transformer.

Internal Weak-Link Fuse

The optional internal weak-link fuse is a fluid-im-

mersed expulsion fuse that is designed to isolate the

transformer from the distribution system in the event

of an overload or an internal transformer fault on the

load side of the fuse. The fuse is mounted at the

bottom of the high-voltage bushing or in some cases

on a terminal block located on the multiple-voltage

switch or between the high-voltage bushing and the

high-voltage coil. The presence of a weak-link fuse, if

provided, will be indicated on the transformer name-

plate.
Fuses can be accessed by removing the transformer

cover or, if a handhole is provided, by removing the

handhole cover. When accessing the fuse, observe

the precautions and instructions discussed in “Open-

ing the Transformer Tank.”

Partial-Range Current-Limiting Fuse

The optional partial-range current-limiting fuse is

designed to limit the energy released by a low-im-

pedance (high-current) internal fault and reduce the

likelihood of violent transformer failure. A weak-link

expulsion fuse is normally installed in series with the

partial-range current-limiting fuse. The purpose of

the weak-link expulsion fuse is to clear a high-imped-

ance fault or overload. When properly applied, the

partial-range current-limiting fuse will operate only

for internal transformer faults. When a partial-range

current-limiting fuse has operated, the transformer

should be considered faulted and removed from ser-

vice. The presence of a partial-range current limiting

fuse, if provided, will be indicated on the transformer

nameplate.

Surge Arrester

The optional surge arrester is used to protect the

transformer from damage due to over-voltage tran-

sients (such as lightning surges), which propagate

through the distribution system. Surge arresters may

be provided as an externally-mounted device or as

an internal fluid-immersed device. The surge arrester

should be installed only on systems where the power

frequency voltage at the arrester does not exceed

the arrester’s published maximum continuous oper-

ating voltage (MCOV) value.

External Surge Arrester

The external arrester line-lead and tank grounding

connections should be checked to ensure they are

tight before placing the transformer in service. Refer

to Table 3 for torque guidelines.

!

WARNING

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW COULD RESULT IN DEATH OR SERIOUS

PERSONAL INJURY, AND COULD ALSO RESULT

IN DAMAGE TO THE EQUIPMENT.
• De-energize the transformer from a remote

location and make sure all transformer

terminals and bushings have zero voltage

before connecting or servicing surge

arresters.

• Disconnect all surge arresters before

performing impulse, induced-potential or

applied-potential tests.

Disconnect the external surge arrester line-lead

before performing impulse, induced-potential or

applied-potential tests; otherwise, the arrester may

be damaged. Reconnect the surge arrester after

testing and before placing the transformer back into

service.

Internal Surge Arrester

The optional internal metal-oxide-varister (MOV)

Advertising