Fluid-Filled Overhead Distribution Transformers

general guide for operation of the Magnex Interrupt-

er. Personnel should read and follow Cooper Power

Systems Magnex Interrupter Installation Instructions

S240-34-1.

The operating handle is located on the side of the

transformer tank and is designed to be operated

with a live-line tool (hot stick), as follows.

− To open the interrupter, rotate the handle

upward in a counterclockwise direction,

until the spring-loaded contacts open and

the handle is in the OPEN position.

− To close the interrupter, rotate the handle

downward in a clockwise direction, until the

handle is against the physical stop in the

CLOSED position. When in the CLOSED po-

sition, the interrupter will operate automati-

cally due to an over-current condition or rise

in oil temperature.

− To reset the interrupter after it has tripped,

rotate the handle upward in a counterclock-

wise direction to the OPEN position, and

then downward in a clockwise direction,

until the handle is against the physical stop

in the CLOSED position.

An optional trip indicator is available, consisting of

an indicator lens which appears orange when the

interrupter is in the TRIPPED position.

Some Magnex Interrupters are supplied with an

optional emergency overload setting. The emergency

overload will allow approximately 30% overload be-

fore tripping. Using a live-line tool (hot stick), operate

the emergency overload as follows.

− To enable emergency overload, rotate the handle

upward in a counterclockwise direction, until the

handle is in the OPEN position. Next, turn the

emergency overload lever counterclockwise to

the EO position. Then rotate the handle down-

ward in a clockwise direction, until the handle is

in the CLOSED position.

− To disable emergency overload, rotate the

handle upward in a counterclockwise direction,

until the handle is in the OPEN position. Next,

turn the emergency overload lever clockwise to

the NORMAL position. Then rotate the handle

downward in a clockwise direction, until the

handle is in the CLOSED position.

The Magnex Interrupter does not provide a visible

disconnect and should not be relied on as the sole

indication that the transformer secondary terminals

are de-energized.

!

WARNING

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW COULD RESULT IN DEATH OR SERIOUS

PERSONAL INJURY, AND COULD ALSO RESULT

IN DAMAGE TO THE EQUIPMENT.
• Do not rely solely on the Magnex interrupter

to de-energize the transformer secondary.

Always ground the secondary terminals

before performing work.

• Operate the Magnex Interrupter with a live-

line tool (hot stick or shotgun stick). Never

operate by hand.

• Do not operate the Magnex Interrupter if

there is evidence of tank distress or leaking.

• The handle must be rotated fully against the

stop in the CLOSED position.

Other Switching and Protective Devices

Overhead transformers may be provided with

switching and protective devices not discussed

in these instructions. In such cases, contact the

Howard Industries Transformer Division or the device

manufacturer for instructions.