Single-Phase Pad-Mounted Compartmental-Type Distribution Transformers

with the universal bushing wells. Do not use

incompatible or improperly rated bushing inserts,

or equipment damage could occur. When installing

inserts, follow the manufacturer’s instructions

accompanying the inserts. Insulated dead-end caps

or plugs must be installed on all unused high-voltage

bushings before energizing. Shipping dust caps must

never be used in place of insulated dead-end caps or

plugs.

Live-front transformers are equipped with high-

voltage bushings having tin-plated eye-bolt or spade

terminals that are suitable for connection with either

aluminum or copper conductors to the high-voltage

source.

Low-Voltage Terminals

Single-phase pad-mounted transformers are usually

provided with externally-clamped, molded, low-

voltage bushings, with or without NEMA standard

spade terminals. When threaded terminals are

installed, a backup nut should be installed and

tightened against the terminal to ensure an

adequate connection that will not loosen or overheat.

Secondary line leads should be securely attached to

the terminals to ensure a low-resistance connection.

Space-Saver

style transformers may be provided

with a block-mounted, wire-lead, low-voltage

termination instead of molded bushings. These wire

leads are designed to be crimp-connected to the

load leads.