Danger, Warning – Howard HI-104 Single-Phase Pad Transformer User Manual

Page 12

Advertising
background image

Document 2.4.96, Revision 0

March, 2013

12

Single-Phase Pad-Mounted Compartmental-Type Distribution Transformers

Pre-Energization Inspection and Tests

After the transformer has been installed, but before

it is energized, the following tests and checks should

be performed at a minimum to ensure that the

transformer is ready to be energized. Do not energize

the transformer without performing these tests and
checks.

!

DANGER

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW WILL RESULT IN DEATH OR SERIOUS

PERSONAL INJURY, AND COULD ALSO RESULT

IN DAMAGE TO THE EQUIPMENT

.

Be aware of dangerous voltages within the ter-

minal compartment and avoid personal contact

with live terminals.

!

WARNING

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW COULD RESULT IN DEATH OR SERIOUS

PERSONAL INJURY, AND COULD ALSO RESULT

IN DAMAGE TO THE EQUIPMENT.
• Only qualified personnel with appropriate

equipment should measure transformer volt-

ages.

• Wear personal protective equipment (PPE)

to prevent injury from potential arc-flash or

contact with dangerous voltages.

• Make sure the transformer is securely and

effectively grounded at all times.

• Insulated dead-end caps or plugs must be

installed on all unused dead-front high-volt-

age bushings. Dust caps must not be used in

place of insulated dead-end caps or plugs.

• Current transformer (CT) leads must be con-

nected to a metering load or shorted together

and grounded to prevent dangerous voltage

at the CT terminals.

• After successful completion of the recom-

mended tests and checks, energize the trans-

former from a remote location.

1. Ratio Test—Using a transformer turns ratio tester

(TTR), perform a ratio test to verify the primary-

to-secondary winding ratio. The measured value

should be within 0.5% of the voltage ratio in-

dicated on the transformer nameplate. If the

transformer is provided with high-voltage taps,

measure the ratio at each tap position to en-

sure that each of the ratios is correct. Follow the

instructions and safety precautions provided by

the TTR equipment manufacturer. For additional

information about ratio testing, refer to IEEE

Standard C57.12.90.

2. Insulation Resistance Test—Perform a 1,000-Volt

insulation test (Megger test) to measure the re-

sistance of the insulation between windings and

from each winding to ground. Follow the instruc-

tions and safety precautions provided by the test

equipment manufacturer. Prior to the test, bush-

ings must be thoroughly cleaned with denatured

alcohol to remove any moisture or contaminants

that could influence the test results. Measured

resistance should be at least 1.0 GΩ.

3. Tap Changer Setting—On transformers pro-

vided with taps, check the tap changer setting

to ensure it is set to the proper position for the

required voltage.

4. Multiple-Voltage Switch Setting—On transform-

ers provided with a multiple-voltage switch,

check the switch setting to make sure it is set to

the correct position.

5. Grounding—Check to ensure that the transformer

tank is securely and effectively grounded. The

transformer tank ground pad is located inside

the terminal compartment near the bottom of the

tank.

6. Bolted Connections—Check all bolted connec-

tions for tightness, referring to nominal torque

guidelines contained in Tables 1 through 4.

7. Fluid Level—Check to make sure the fluid level

is correct as indicated by the fluid level gauge or

sight plug. If the transformer does not have a flu-

id level gauge or sight plug, the fluid level can be

checked by temporarily removing the liquid-level

plug located at the 20°C mark. Prior to removing

the plug, relieve tank pressure by operating the

SECTION 4: INSPECTION AND TESTING BEFORE AND

AFTER INITIAL ENERGIZATION

Advertising