Warning – Howard HI-104 Single-Phase Pad Transformer User Manual

Page 30

Advertising
background image

Document 2.4.96, Revision 0

March, 2013

30

Single-Phase Pad-Mounted Compartmental-Type Distribution Transformers

4. Fluid quality tests, such as moisture content,

power factor, dielectric strength and dissolved gas

analysis.

Exterior Paint Finish

Any damage to the exterior paint finish that exposes

the primer coat or bare metal should be repaired

immediately in order to prevent corrosion. Areas

to be repaired should be thoroughly clean and dry.

The surface should be sanded to remove rust, loose

paint flakes and other debris. The surface should

then be cleaned with a suitable solvent to remove

any oil, grease or other contaminants. At lease two

coats of high-quality touchup paint should be applied

to the damaged area. Bare metal should receive a

primer coat before applying the final finish. Touch-up

paint is available from the Howard Industries Trans-

former Division.

Fluid Leaks

Check the tank for indication of fluid leaks, looking

carefully at weld seams and at tank fittings, such

as bushings, gauges, plugs and valves. Fluid leaks

should be repaired as soon as possible to prevent

moisture contamination of the insulating fluid and to

prevent internal flashover due to low fluid level.

!

WARNING

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW COULD RESULT IN DEATH OR SERIOUS

PERSONAL INJURY, AND COULD ALSO RESULT

IN DAMAGE TO THE EQUIPMENT.
• De-energize transformer from a remote

location before performing any inspection or

maintenance work.

• Make sure all transformer terminals and

bushings have zero voltage.

• Make sure that the transformer is properly

grounded.

• Fluid leaks should be repaired as soon as

they are discovered.

If a fluid leak is suspected, investigate thoroughly to

determine if an actual leak does exist on the trans-

former. False indications of a leak can occur as a re-

sult of residual fluid that was not sufficiently cleaned

after the transformer was filled with fluid. In some

cases silicone lubricant used to install high-voltage

bushing inserts can flow onto the front panel, giving

a false indication of a fluid leak.

In addition to the presence of fluid residue, a low

reading on the optional fluid level gauge and a con-

stant zero reading on the optional pressure/vacuum

gauge (which does not vary over time as a function

of transformer loading and ambient temperature) are

also indications of a possible fluid leak.

To verify that a fluid leak does exist, clean the sus-

pected leak area with an appropriate solvent to

completely remove the fluid and observe the area

for reappearance of fluid. To accelerate the test,

pressurize the tank with dry air or nitrogen through

the pressure test fitting to a pressure of 3-4 PSIG.

Let the tank stand under pressure for one to two

hours, then inspect for leaks. Leaks above the fluid

level can be detected by applying soap solution to all

welds, joints, pipe fittings, and cable connections.

In many cases a small pin-hole tank leak or leak

from a bushing, gauge, valve or other fitting can be

repaired on site. Pin-hole and weld seam leaks can

usually be repaired by welding on a de-energized

transformer. Welding on panel-type radiators is not

recommended due to the thin gauge material used

in its construction. Very small pin-hole leaks can

sometimes be repaired using an epoxy patch kit

designed to repair fluid leaks.

Bushing leaks can sometimes be corrected by

tightening the bushing clamp bolts. Do not exceed

the recommended torque values listed in Table 2 to

prevent the possibility of bushing or gasket damage.

Audible Sound Level

It is normal for transformers to emit an audible hum-

ming sound, which is primarily caused by alternating

magnetic flux in the transformer core. Amplitude

and harmonic content of the sound is influenced by

transformer size, the energizing voltage level and

sinusoidal purity, load conditions and acoustic condi-

tions at the installation site. Unusual sounds should

be investigated, as this might indicate a potential

problem.

Refer to NEMA Standards Publication TR-1 Trans-

formers, Regulators and Reactors, and IEEE Stan-

Advertising