Howard HI-104 Single-Phase Pad Transformer User Manual

Page 7

Advertising
background image

Document 2.4.96, Revision 0

March, 2013

7

Single-Phase Pad-Mounted Compartmental-Type Distribution Transformers

Before unloading the transformer, the following

checks should be performed:

1. Read the serial number on the transformer

nameplate and make sure it matches

the serial number listed on the shipping

documents. Also, check the nameplate

for kVA rating, high-voltage rating, low-

voltage rating, impedance and other design

characteristics, and make sure they comply

with the specifications.

2. Check shipping documents to make sure

the shipment is complete, including all listed

accessories and hardware. Be aware that

additional items may arrive on separate

pallets. Claims for shortages or errors

must be noted on the shipping documents

and reported immediately to the Howard

Industries Transformer Division. Failure

to make a timely claim will constitute

unqualified acceptance and a waiver of all

such claims by the purchaser.

3. The tank vacuum/pressure gauge, when

provided, may indicate a positive or negative

reading when the transformer is received,

depending on the relative temperatures of

the fluid and ambient air. A rising or falling

reading that varies over time with ambient

temperature indicates that the transformer

tank is sealed effectively. If the vacuum/

pressure gauge shows a constant zero

reading, this indicates the possibility of a

tank leak. If this occurs, the tank should be

checked carefully for leaks as indicated in

the following step.

4. Check the tank for indication of fluid leaks,

looking carefully at weld seams, bushings,

gauges, valves and all other tank fittings. If

suspicious indications are found, investigate

thoroughly to determine if a leak does

exist on the transformer. Indications of a

leak can sometimes be residual fluid that

was not cleaned during the manufacturing

process and not an actual leak. In many

cases a small pinhole tank leak or leak

from a bushing, gauge, valve or other fitting

can be easily repaired on site. Refer to

the “Maintenance and Repair” section for

information about the repair of fluid leaks.

5. Check for external damage including dents

or scratches on the tank walls, radiators and

terminal compartment. Dents and scratches

can often be repaired on site using simple

touch-up procedures. If touch-up painting

is performed, do not remove or obscure

any warning labels, instructional labels or

nameplates.

6. Check for broken, cracked, or damaged

bushings, gauges, valves and other fittings

and accessories.

7. Check for missing or damaged component

parts and for packages that shipped

separately from the transformer.

Fluid Level

The transformer is shipped from the factory with

insulating fluid filled to the proper level. Before

energizing the transformer, verify proper fluid level

by observing the fluid level gauge, if provided. The

fluid level gauge pointer should be between the

“High” and “Low” marks. For transformers provided

with a fluid sight plug, the fluid level can be directly

observed if it is within acceptable range. If the

transformer does not have a fluid level gauge or sight

plug, the fluid level can be checked by removing

the liquid level plug located at the 25°C mark. Prior

to removing the fill plug, relieve tank pressure by

operating the PRV, being careful to avoid any hot

fluid that might be expelled from the valve. Exercise

caution when checking the fluid level using the

fluid level plug, as the fluid may spill out and may

be extremely hot. When reinstalling the fill plug,

apply a suitable sealing compound to the threads to

ensure a proper seal. When checking the fluid level,

be aware that the level will vary as a function of fluid

temperature.

A transformer found to have a low fluid level should

be checked for potential leaks and filled to the

proper level with the same type of liquid as that

specified on the transformer nameplate. Refer to

“Filling with Fluid.”

Advertising