Howard HI-104 Single-Phase Pad Transformer User Manual

Page 31

Advertising
background image

Document 2.4.96, Revision 0

March, 2013

31

Single-Phase Pad-Mounted Compartmental-Type Distribution Transformers

dard C57.12.90 Test Code for Liquid-Immersed

Distribution, Power, and Regulating Transformers for

more information about design sound levels and fac-

tory sound testing.

Low-Voltage Circuit Breaker

The low-voltage circuit breaker is inaccessible (ex-

cept in the double-door style transformer) and typi-

cally requires no maintenance.

Magnex Interrupter

The Magnex Interrupter typically requires no mainte-

nance except for replacement in the event of mal-

function or damage.

Other Accessory Devices

Other accessory devices, such as a gauges and

valves typically require no maintenance except for

replacement in the event of malfunction or damage.

Sampling and Testing the Fluid

Before sampling the insulating fluid, de-energize the

transformer from a remote location and make sure

all bushings and terminals are effectively grounded.

Samples should be drawn from the bottom of the

tank. Refer to ASTM D923 Standard Practices for

Sampling Electrical Insulating Liquids for recom-

mended sampling procedures. Also, refer to any

sampling recommendations provided by the manu-

facturer of the fluid test equipment.

Filtering the Fluid

The insulating fluid can be filtered using a filter press

system. A filter press can remove particle contami-

nants as well as small amounts of moisture. Follow

the operating instructions provided by the filter press

system manufacturer.

Continue to filter the fluid until the dielectric test

results satisfy the requirements of IEEE Standard

C57.106 for mineral oil, IEEE Standard C57.147 for

natural ester fluids and IEEE Standard C57.212 for

transformers filled with less-flammable high mo-

lecular weight hydrocarbon insulating fluid (such as

R-Temp). When filtering any particular type of insu-

lating fluid, make sure the filter press system is not

contaminated with any other type of fluid. Contami-

nation of the fluid may alter its chemical or physical

characteristics and could reduce its fire point.

Removing or Lowering the Fluid

Should it be necessary to remove or lower the insu-

lating fluid, the following procedure should be used.

Use clean pumps and hoses that have not been

contaminated by other types of fluids. Hoses must

be designed for handling the particular fluid in the

transformer (As an example, rubber hoses should not

be used with mineral oil.).
1. De-energize the transformer, and make sure the

tank and all terminals are effectively grounded.

2. If cover removal is required, follow the procedure

outlined in the “Opening the Transformer Tank”

section.

3. Connect the pump inlet hose to the drain valve at

the base of the transformer tank. In the case of a

double-door style transformer, the inlet hose can

be inserted through the cover-mounted handhole

and placed at the bottom of the tank.

4. Use a clean, dry temporary storage container to

contain the fluid.

5. Place the pump discharge hose nozzle at the bot-

tom of storage container.

6. Pump slowly, and do not allow the fluid to splash

into the container, as this will introduce air and

moisture into the fluid.

7. Do not lower the insulating fluid below the top of

the core/coil clamp pan, as exposing coils could

allow moisture to contaminate coil insulation.

Filling with Fluid

When filling the transformer with insulating fluid,

fill with the same type of fluid. Do not mix different

types of fluids. Care should be taken to avoid intro-

duction of air bubbles during the filling process. After

filling is complete, allow 24 hours for dissipation

of air bubbles before energizing the transformer.

Trapped air bubbles can reduce the insulation value

of the fluid and cause an internal flash-over.
1. Every storage container of transformer fluid used

in the filling process should be visually inspected

and tested for water and other possible contami-

nants before proceeding with the filling process.

2. Pump from the bottom of storage container. To

prevent bubbles in the fluid, do not allow air to

enter the pump intake.

3. Connect the pump discharge hose to the drain

valve at the base of the transformer tank to

Advertising