Single-Phase Pad-Mounted Compartmental-Type Distribution Transformers

!

WARNING

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW COULD RESULT IN DEATH OR SERIOUS

PERSONAL INJURY, AND COULD ALSO RESULT
IN DAMAGE TO THE EQUIPMENT.
• Do not energize the transformer if the fluid

level is low.

• Maintain proper fluid level at all times while

the transformer is energized.

• Exercise caution when checking the fluid level

with the fluid level plug, as the fluid may spill

and may be extremely hot.

Internal Inspection

An internal inspection of the transformer tank is

rarely necessary and is recommended only when

there are obvious indications that the transformer

has received severe impact damage during transit

or when necessary to perform recommended pre-

energization tests or inspections. Do not open

the transformer tank without authorization from

the Howard Industries Transformer Division. If the

transformer tank must be opened, refer to “Opening

the Transformer Tank” for instructions.

Fluid Sampling

Sampling and testing of the fluid is not required

unless there is indication that moisture or other

contaminants have accidently entered the tank

during transit. If moisture or contaminants in the

fluid is suspected, contact the Howard Industries

Transformer Division immediately for instructions.

If fluid sampling is required, refer to “Sampling the

Fluid” for instructions.

Transformer Storage

Transformers may be temporarily stored if properly

prepared. It is recommended that transformers

be stored completely assembled. Prior to storage,

transformers should be thoroughly inspected as

described above in the “Initial Inspection” section.

If the transformer is not completely assembled,

separate components and accessories should be

stored in a clean dry area in their original shipping

containers. Do not store the transformer in a

corrosive environment.

Transformers should be stored on a firm level

surface. They may also be stored in racks designed

for that purpose. Transformers should not be stacked

directly on top of one another, as this may damage

the paint finish and cause cabinet misalignment.

It is recommended that the transformer be inspected

periodically while it is in extended storage. Ensure

that an effective pressure seal is maintained, and

check for leaks and corrosion. Any damage or

defects should be repaired immediately.