Single-Phase Pad-Mounted Compartmental-Type Distribution Transformers

sure the cabinet is secure and tamper

proof. Make sure the transformer and sill

are sitting flush on the mounting pad with

no gaps that might allow entry of a foreign

object into the terminal compartment.

Double-Door Terminal Compartment

The double-door style pad-mounted transformer is

designed with a terminal compartment consisting of

a terminal compartment cover, two hinged doors and

a base sill. The secondary-side door can be opened

by removing the padlock, disengaging the penta-

head security bolt and rotating the door handle. The

primary-side door may be fastened with one or more

security bolts, which must be disengaged to open the

door. Latch rods located at the bottom of each door

can be used to secure doors in the open position.

The double-door style pad-mounted transformer may

also be equipped with a flip-top terminal compart-

ment cover, which can be raised to facilitate opera-

tion of the optional Bay-O-Net fuse and to provide

clearance for pulling cables into the terminal com-

partment. To open the cover, disengage the center

security bolt and rotate the cover upward. A latch is

provided to secure the cover in the open position.

Lift-off door hinges are provided on double-door style

pad-mounted transformers, so that the compartment

doors can be removed when in the open position.

Before leaving the installation site, make sure the

terminal compartment is closed and secure, using

the following procedure.

− Close the flip-top cover, if present.

− Close the primary compartment door and

engage each security bolt.

− Close the secondary compartment door

and turn the handle to the closed posi-

tion. Fully engage the secondary compart-

ment door security bolt.

− Install a suitable heavy-duty padlock.

− Carefully check the transformer to make

sure the cabinet appears to be secure

and tamper proof. Make sure the trans-

former and sill are sitting flush on the

mounting pad with no gaps that might

allow entry of a foreign object into the

terminal compartment.

Other Accessory Devices

Transformers may be provided with accessory devic-

es not discussed in these instructions. In such cases

contact the Howard Industries Transformer Division if

additional information is needed.