Danger, Warning – Howard HI-104 Single-Phase Pad Transformer User Manual

Page 13

Advertising
background image

Document 2.4.96, Revision 0

March, 2013

13

Single-Phase Pad-Mounted Compartmental-Type Distribution Transformers

pressure relief valve, being careful to avoid any

hot fluid that might be expelled from the valve.

When reinstalling the plug, apply an appropriate

thread sealing compound to prevent a fluid leak.

Be aware that fluid temperature and orientation

of the transformer tank will cause the fluid level

to vary. Transformers are filled to a level that

corresponds to a fluid temperature of 25°C. The

actual fluid level will increase with increasing

temperature. The fluid level indication will also

vary when the transformers is not installed in a

level orientation.

8. Fluid Temperature—Observe the fluid tempera-

ture gauge and make sure the temperature is

no lower than indicated below before the unit is

energized.

-20°C (-4°F) for conventional transformer oil

and silicone fluid

0°C (32°F) for R-Temp fluid

-10°C (14° F) for natural ester fluid

9. Internal Fault Detector—If the transformer is

provided with an Internal Fault Detector (IFD),

remove the red shipping lock after installation

and before placing the transformer into service.

10. Current Transformers—If current transformers

(CTs) are present, connect CT leads to the meter-

ing load. If CT leads are not connected to a me-

tering load, they must be shorted together and

grounded before the transformer is energized.

11. Accessory Wiring—Check wiring of control and

alarm circuits (if provided) to make sure there

are no loose connections and no damage to wire

insulation.

12. Tank Finish—Check all painted surfaces to make

sure that there is no damage or corrosion.

13. Tools—Check to make sure that all tools and

equipment are accounted for.

14. Internal Inspection— Transformer tanks are

sealed at the factory and should not be opened

unless necessary. Single-door style transformer

tanks are fully welded and are not accessible

except through bushing openings. Double-door

style transformer tanks are accessible through

a bolted handhole located on the tank cover. If

the transformer tank must be accessed, refer to

“Opening the Transformer Tank” for instructions.

Post-Energization Inspection and Tests

After the transformer is energized, the following tests

and inspections should be performed.

!

DANGER

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW WILL RESULT IN DEATH OR SERIOUS

PERSONAL INJURY, AND COULD ALSO RESULT

IN DAMAGE TO THE EQUIPMENT

.

Be aware of dangerous voltages within the ter-

minal compartment and avoid personal contact

with live terminals.

!

WARNING

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW COULD RESULT IN DEATH OR SERIOUS

PERSONAL INJURY, AND COULD ALSO RESULT

IN DAMAGE TO THE EQUIPMENT.
• Energize the transformer from a remote loca-

tion.

• Only qualified personnel with appropriate

equipment should measure transformer volt-

ages.

• Wear personal protective equipment (PPE)

to prevent injury from potential arc-flash or

contact with dangerous voltages.

• Make sure the transformer is securely and

effectively grounded at all times.

• Insulated dead-end caps or plugs must be

installed on all unused dead-front high-volt-

age bushings. Dust caps must not be used in

place of insulated dead-end caps or plugs.

• Current transformer (CT) leads must be con-

nected to a metering load or shorted together

and grounded to prevent dangerous voltage

at the CT terminals.

1. Verifying Correct Voltage—Before supplying volt-

age from the transformer to the load, verify that

the secondary voltage is correct. Using a suitable

AC voltmeter, measure the voltage of the sec-

ondary windings and make sure they agree with

the secondary voltage listed on the transformer

nameplate.

Advertising