CAUTION:

DO NOT redrill orifices. Improper drilling

(burrs, out-of-round holes, etc.) can cause excessive
burner noise and misdirection of burner flames. This can
result in flame impingement of burners and heat exchang-
ers, causing failures.

(3.) After correct manifold pressure is obtained, replace

gas valve regulator adjustment screw cap and verify
adjusted gas input rate using method outlined in
item c.

(4.) Burner flame should be clear blue, almost transpar-

ent. (See Fig. 13.)

c. Verify natural gas input rate by clocking gas meter.

NOTE:

High-Altitude Adjustment

UNITED STATES
At installation altitudes above 2000 ft, this furnace has been
approved for a 4 percent derate for each 1000 ft above sea level.
See Table 7 for derate multiplier factor.

CANADA
At installation altitudes from 2000 to 4500 ft, this furnace must be
derated 10 percent by an authorized Gas Conversion Station. To
determine correct input rate for altitude, see example above and
use 0.90 as derate multiplier factor.

d. Turn off all other gas appliances and pilots.

e. Start furnace and let operate for 3 minutes.

f. Measure time (in sec) for gas meter test dial to complete

1 revolution.

TABLE 6—MODEL 395CAV ORIFICE SIZE* AND MANIFOLD PRESSURE FOR CORRECT INPUT (CONTINUED)

(TABULATED DATA BASED ON 22,000 BTUH PER BURNER, DERATED 4 PERCENT FOR EACH 1000 FT ABOVE SEA LEVEL)

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

9001

to

10,000

575

43

2.7

43

2.8

43

2.9

43

3.0

43

3.1

600

43

2.5

43

2.6

43

2.7

43

2.7

43

2.8

625

43

2.3

43

2.4

43

2.4

43

2.5

43

2.6

650

43

2.1

43

2.2

43

2.3

43

2.3

43

2.4

675

48

3.7

43

2.0

43

2.1

43

2.2

43

2.2

700

48

3.4

48

3.6

48

3.7

43

2.0

43

2.1

725

49

3.8

48

3.3

48

3.4

48

3.5

48

3.6

750

49

3.5

49

3.6

49

3.8

48

3.3

48

3.4

775

49

3.3

49

3.4

49

3.5

49

3.6

49

3.7

* Orifice numbers shown in shading are factory installed

A93059

BURNER

ORIFICE

EXAMPLE:

88,000 BTUH INPUT FURNACE INSTALLED AT 4300 FT.

Furnace Input

Rate at

Sea Level

Derate

Multiplier

Factor

Furnace Input Rate

at Installation Altitude

X

=

88,000

X

0.82

=

72,160

TABLE 7—ALTITUDE DERATE MULTIPLIER FOR U.S.A.

ALTITUDE

(FT)

PERCENT OF

DERATE

DERATE MULTIPLIER

FACTOR FOR U.S.A.*

0-2000

0

1.00

2001-3000

8-12

0.90

3001-4000

12-16

0.86

4001-5000

16-20

0.82

5001-6000

20-24

0.78

6001-7000

24-28

0.74

7001-8000

28-32

0.70

8001-9000

32-36

0.66

9001-10,000

36-40

0.62

* Derate multiplier factor is based on midpoint altitude for altitude range.

Fig. 12—Redundant Automatic Gas Control Valve

A00238