Bryant 395CAV User Manual

Page 7

Advertising
background image

bottom return application. See Table 3 to determine correct filter
size for desired filter location. Table 3 indicates filter size,
location, and quantity shipped with the furnace.

For bottom air-return applications, filter may need to be cut to fit
some furnace casing widths. A bottom closure panel is factory
installed in the bottom of the furnace. When bottom return inlet is
desired, remove and discard the bottom closure panel. Two sets of
hardware are needed for furnaces in 24-1/2-in. wide casings using
2 filters for bottom return. All hardware is provided for filter
installation.

CAUTION:

Use care, when cutting support rods in

filters, to protect against flying pieces and sharp rod ends.
Wear safety glasses, gloves, and appropriate protective
clothing. Failure to follow this caution could result in
personal injury.

NOTE:

Furnaces with a 17-1/2-in. wide casing require an addi-

tional procedure when locating the filter for bottom return-air
application. Field fabricate a sheet metal filler strip 1 X 3 X 24-1/2
in. and install it along side of the filter as shown in Fig. 6. Drive
2 screws through the casing side and into the filler strip to secure
it in place. Filter should rest on the top of the filler strip when
installed.

III.

LEVELING LEGS (IF REQUIRED)

When furnace is used with side inlet(s) and leveling legs are
required, refer to Fig. 7 and install field-supplied, corrosion-
resistant 5/16-in. machine bolts and nuts.

NOTE:

The maximum length of the bolt should not exceed 1-1/2

in.

1. Lay furnace on its back. Locate and drill a 5/16-in. diameter

hole in each bottom corner of furnace as shown in Fig. 7.

A93043

FRONT

BACK

FRONT

B
A
C
K

Fig. 5—Side Filter Arrangement

(Control Removed for Clarity)

A93045

FILTER
RETAINER

WASHABLE

FILTER

TABLE 3—FILTER INFORMATION (IN.)

AIR FILTER LOCATED IN BLOWER COMPARTMENT

FURNACE

CASING

WIDTH (IN.)

FILTER SIZE (IN.)*

FILTER

TYPE

Side Return

Bottom Return

14-3/16

(1) 16 X 25 X 1†

(1) 14 X 25 X 1

Cleanable

17-1/2

(1) 16 X 25 X 1†

(1) 16 X 25 X 1† Cleanable

21

(1) 16 X 25 X 1

(1) 20 X 25 X 1† Cleanable

24-1/2

(1 or 2) 16 X 25 X 1 (1) 24 X 25 X 1† Cleanable

* Filters may be field modified by cutting filter material and support rods (3) in
filters. Alternate sizes and additional filters may be ordered from your dealer.
† Factory-provided with furnace.

Fig. 6—Bottom Filter Arrangement (Control Removed for

Clarity)

A00290

WASHABLE
FILTER

FILTER
SUPPORT

FILTER
RETAINER

17

1

2

-IN. WIDE

CASINGS ONLY:
INSTALL FIELD-SUPPLIED
FILTER FILLER STRIP
UNDER FILTER.

1

24

1

/

2

3

21-IN. WIDE
CASINGS ONLY:
SUPPORT RODS (3)
EXTEND 1/4" ON EACH
SIDE OF FILTER AND
REST ON CASING FLANGE

—7—