Bryant 395CAV User Manual

Page 17

Advertising
background image

g. Refer to Table 8 for cu ft of gas per hr.

h. Multiply gas rate (cu ft/hr) X heating value (Btu/cu ft)

using natural gas heating value from local gas
utility/supplier.

EXAMPLE: (0–2000 ft altitude)
Furnace input from rating plate is 110,000
Btu heating input = Btu/cu ft X cu ft/hr
Heating value of gas = 1050 Btu/cu ft
Time for 1 revolution of 2-cu ft dial = 70 sec
Gas rate = 103 cu ft/hr (from Table 8)
Btu heating input = 103 X 1050 = 108,150 Btuh
In this example, the orifice size and manifold pressure
adjustment is within ±2 percent of the furnace input rate.

2. Set temperature rise.

Furnace must operate within range of temperature rise
specified on the furnace rating plate. Determine the air
temperature rise as follows.

a. Place duct thermometers in return and supply ducts as

near furnace as possible. Be sure thermometers do not
“see” heat exchangers so that radiant heat will not affect
thermometer readings. This is particularly important
with straight-run ducts.

b. When thermometer readings stabilize, subtract return-air

temperature from supply-air temperature to determine
temperature rise.

c. Adjust air temperature rise by adjusting blower speed.

Increase blower speed to reduce temperature rise. De-
crease blower speed to increase temperature rise.

WARNING:

Disconnect the electrical power before

changing the speed tap. A failure to follow this warning
can cause personal injury.

d. To change blower motor speed selections for heating

mode, remove blower motor lead from control HEAT
terminal. (See Fig. 10.) Select desired blower motor
speed lead from 1 of the other terminals and relocate it
to HEAT terminal. See Table 9 for lead color identifi-
cation. Reconnect original lead on SPARE terminal.

CAUTION:

If Model 376CAV066115 is installed in

0.50-in. wc or lower static pressure ductwork, evaporator
coil condensate blow off can occur during cooling opera-
tion. When installed in this manner, do not use high
blower speed tap for cooling.

CAUTION:

Recheck temperature rise. It must be within

limits specified on unit rating plate. Recommended op-
eration is at midpoint of rise or above.

3. Set thermostat heat anticipator.

The thermostat heat anticipator must be set to match the
amp draw of the electrical components in the R-W circuit.
Accurate amp draw readings can be obtained at thermostat
subbase terminals R and W. Fig. 14 illustrates an easy
method of obtaining the actual amp draw. The amp reading
should be taken after the blower motor has started. See the
thermostat manufacturer’s instructions for adjusting the
heat anticipator and for varying the heating cycle length.

Fig. 13—Burner Flame

A89020

;;

;;

BURNER FLAME

BURNER

MANIFOLD

TABLE 8—GAS RATE (CU FT/HR)

SECONDS

FOR 1

REVOLUTION

SIZE OF TEST DIAL

SECONDS

FOR 1

REVOLUTION

SIZE OF TEST DIAL

1

Cu Ft

2

Cu Ft

5

Cu Ft

1

Cu Ft

2

Cu Ft

5

Cu Ft

10

360

720

1800

50

72

144

360

11

327

655

1636

51

71

141

355

12

300

600

1500

52

69

138

346

13

277

555

1385

53

68

136

340

14

257

514

1286

54

67

133

333

15

240

480

1200

55

65

131

327

16

225

450

1125

56

64

129

321

17

212

424

1059

57

63

126

316

18

200

400

1000

58

62

124

310

19

189

379

947

59

61

122

305

20

180

360

900

60

60

120

300

21

171

343

857

62

58

116

290

22

164

327

818

64

56

112

281

23

157

313

783

66

54

109

273

24

150

300

750

68

53

106

265

25

144

288

720

70

51

103

257

26

138

277

692

72

50

100

250

27

133

267

667

74

48

97

243

28

129

257

643

76

47

95

237

29

124

248

621

78

46

92

231

30

120

240

600

80

45

90

225

31

116

232

581

82

44

88

220

32

113

225

563

84

43

86

214

33

109

218

545

86

42

84

209

34

106

212

529

88

41

82

205

35

103

206

514

90

40

80

200

36

100

200

500

92

39

78

196

37

97

195

486

94

38

76

192

38

95

189

474

96

38

75

188

39

92

185

462

98

37

74

184

40

90

180

450

100

36

72

180

41

88

176

439

102

35

71

178

42

86

172

429

104

35

69

173

43

84

167

419

106

34

68

170

44

82

164

409

108

33

67

167

45

80

160

400

110

33

65

164

46

78

157

391

112

32

64

161

47

76

153

383

116

31

62

155

48

75

150

375

120

30

60

150

49

73

147

367

TABLE 9—SPEED SELECTOR

COLOR

SPEED

FACTORY-

ATTACHED TO

Black

High

COOL

Yellow (When Present)

Medium-High

SPARE

Blue

Medium-Low

HEAT

Red

Low

SPARE

White

Common

L2/COM

—17—

Advertising