WARNING:

Do not install furnace on its back. Safety

control operation will be adversely affected. Never con-
nect return-air ducts to back of furnace. Failure to follow
this warning could result in fire, personal injury, or death.

II.

FILTER ARRANGEMENT

WARNING:

Never operate unit without a filter or with

filter access door removed. Failure to follow this warning
can cause fire, personal injury, or death.

The air filter arrangement will vary due to application, furnace
orientation, and filter type. The filter may be installed in an
external Filter/Media cabinet (if provided) or the furnace blower
compartment. Factory supplied washable filters are shipped in the
blower compartment.

If a factory-supplied external Filter/Media cabinet is provided,
instructions for its application, assembly, and installation are
packaged with the cabinet. The Filter/Media cabinet can be used
with the factory-supplied washable filter or a factory-specified
high-efficiency disposable filter (see cabinet instructions).

If installing the filter in the furnace blower compartment, deter-
mine location for the filter and relocate filter retaining wire if
necessary. See Fig. 5 for side return application and Fig. 6 for

SUPPLY

AIR

6

MIN

(FRONT)

RETURN AIR

VENT THROUGH ROOF

1 SQ IN.
PER 1000
BTUH* IN DOOR

OR WALL

12

MAX

1 SQ IN.
PER 1000
BTUH* IN DOOR

OR WALL

12

MAX

INTERIOR

HEATED

SPACE

* Minimum opening size is 100 sq in. with
minimum dimensions of 3 in.

Minimum of 3 in. when type-B1 vent is used.

UNCONFINED
SPACE

CONFINED

SPACE

A89012

Fig. 3—Confined Space: Air for Combustion and Ventilation

from an Unconfined Indoor Space

1 SQ IN.

PER

4000

BTUH*

DUCTS

TO

OUTDOORS

1 SQ IN.
PER 4000
BTUH*

SUPPLY

AIR

VENT
THROUGH
ROOF

D

B

A

C

E

1 SQ IN.
PER 4000
BTUH*

DUCT

TO

OUTDOORS

RETURN AIR

1 SQ IN.
PER 2000
BTUH*

1 SQ IN.
PER 2000
BTUH*

DUCTS

TO

OUTDOORS

12

MAX

12

MAX

12

MAX

Use any of the following
combinations of openings:
A & B C & D D & E F & G

NOTE:

*

Minimum dimensions of 3 in.

CONFINED

SPACE

12

MAX

12

MAX

OUTDOORS

1 SQ IN.

PER

4000

BTUH*

F

G

A89013

Fig. 4—Confined Space: Air for Combustion and Ventilation

from Outdoors

TABLE 2—MINIMUM FREE AREA OF COMBUSTION AIR OPENING*

395CAV

FURNACE

INPUT

(BTUH)

AIR FROM INDOOR

UNCONFINED SPACE

OUTDOOR AIR THROUGH

VERTICAL DUCTS

OUTDOOR AIR THROUGH

HORIZONTAL DUCTS

OUTDOOR AIR THROUGH

SINGLE DUCT

Free Area

of Opening

(Sq. In.)

Free Area of

Opening and Duct

(Sq. In.)

Round

Pipe

(In. Dia.)

Free Area

of Opening and Duct

(Sq. In.)

Round

Pipe

(In. Dia)

Free Area

of Opening and Duct

(Sq. In.)

Round

Pipe

(In. Dia)

44,000

100

11.0

4

22.0

6

14.67

5

66,000

100

16.5

5

33.0

7

22.00

6

88,000

100

22.0

6

44.0

8

29.33

7

110,000

110

27.5

6

55.0

9

36.67

7

132,000

132

33.0

7

66.0

10

44.00

8

154,000

154

38.5

8

77.0

10

51.33

9

* Free area shall be equal to or greater than the sum of the areas of all vent connectors in the confined space. Opening area must be increased if other gas appliances in
the space require combustion air.