Installation Instructions

PLUS 95S -- MODEL 355CAV

DIRECT--VENT 4--WAY MULTIPOISE

CONDENSING GAS FURNACE

WITH PERFECT SENSET PERFECT HUMIDITYT

SERIES A

NOTE: Read the entire instruction manual before starting the
installation.
This furnace can be vented as a direct vent (2--pipe) or as an
optional ventilated combustion air application.
Furnaces installed in Canada must use Vent Systems that are

certified to the Standard for Type BH Gas Venting Systems,
ULC--S636.

ULC--S636 certified plastic vent system material or the
components of ULC--S636 certified vent systems must not be

interchanged with other vent systems or unlisted pipe/fittings.

Vent components supplied with the furnace and components in
factory authorized vent kits may be used with ULC--S636

certified vent systems.
The ULC--S636 certified plastic components, and specified

primers and glues of the certified system must be from a

single--system manufacturer and not mixed with other system
manufacturer’s vent system parts.

The first 3 ft. (.91 M) of the venting system must be readily
accessible for inspection.

Some Provinces may require the combustion air system to be
ULC--S636 certified.
NOTE: Please retain these instructions with the furnace after
installation for future reference.

TABLE OF CONTENTS

PAGE

IMPORTANT INFORMATION

2

. . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

3

. . . . . . . . . . . . . . . . . . . . . . . .

CODES AND STANDARDS

6

. . . . . . . . . . . . . . . . . . . . . . . . . .

ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS

7

. .

INTRODUCTION

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

APPLICATIONS

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Upflow

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Downflow

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Horizontal Left

11

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Horizontal Right

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

LOCATION

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION

16

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Air Ducts

19

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Air for Combustion and Ventilation

26

. . . . . . . . . . . . . . . . . .

Combustion Air Pipe

32

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Vent Pipe

34

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Vent Termination

37

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Condensate Drain

42

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START--UP, ADJUSTMENTS, AND SAFETY CHECK

43

. . .

CHECKLIST

59

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ama

CERTIFIED

As an ENERGY STAR® Partner,

Bryant Heating & Cooling has

determined that this product

meets the ENERGY STAR®

guidelines for energy efficiency.

REGISTERED

ISO 9001:2000

UPFLOW

DOWNFLOW

HORIZONTAL

LEFT

AIRFLOW

AIRFLOW

AIRFLOW

AIRFLOW

HORIZONTAL

RIGHT

A93041

Fig. 1 -- Furnace Orientation

FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit damage.
Improper installation or misapplication of furnace may

require excessive servicing or cause premature component

failure. This furnace can be vented as either a direct vent

(2--pipe) furnace or as an optional ventilated combustion air

application.

A direct vent system shall be installed in accordance with

the direct vent (2--pipe) procedures in the Combustion Air

and Vent Pipe Systems section within this instruction. For

optional ventilated combustion air applications, refer to the

ventilated combustion air option procedures in the same

section.
Application of this furnace should be indoors with special

attention given to vent sizing and material, gas input rate,

air temperature rise, unit leveling, and unit sizing.