Warning, Caution – Bryant Condensing Gas 355CAV User Manual

Page 25

Advertising
background image

25

Factory Installed J--Box Location
Install power entry hole filler plugs (factory--supplied in loose

parts bag) in unused power entry holes. (See Fig. 31.)

A05113

FACTORY
INSTALLED
LOCATION

UNUSED 7/8-IN.
DIAMETER POWER
ENTRY HOLES

POWER ENTRY HOLE
FILLER PLUG (FACTORY-
SUPPLIED LOOSE PARTS BAG)

A05113

Fig. 31 -- Factory Installed J--Box Location

J--Box Relocation

1. Remove two screws holding auxiliary J--box. (See Fig.

32.)

2. Rotate J--box 180_ and attach box to left side, using holes

provided.

FACTORY

INSTALLED

LOCATION

ALTERNATE

FIELD

LOCATION

A00212

Fig. 32 -- J--Box Relocation

3. Install power entry hole filler plugs (factory--supplied

loose parts bag) in unused power entry holes. (See Fig.

31.)

FIRE OR ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury, death, or property damage.
If manual disconnect switch is to be mounted on furnace,

select a location where a drill or fastener will not contact

electrical or gas components.

!

WARNING

NOTE:

If modulating dampers are used, blower motor

automatically compensates for modulating dampers. If manual
disconnect switch is to be mounted on furnace, select a location
where a drill or fastener will not contact electrical or gas
components.

24--v wiring
Make field 24--v thermostat connections at 24--v terminal block

on furnace control. Y wire from thermostat MUST be connected
to Y/Y2 terminal on control, as shown in Fig. 19, for proper

cooling operation. The 24--v terminal block is marked for easy
connection of field wiring. (See Fig. 33.) The 24--v circuit

contains a 3--amp, automotive--type fuse located on furnace

control. (See Fig. 33.)
Any electrical shorts of 24--v wiring during installation, service,

or maintenance may cause fuse to blow. If fuse replacement is
required, use only a fuse of identical size (3 amp) and type. The

furnace control will flash status code 24 when fuse needs

replacement.
NOTE: Use AWG No. 18 color--coded copper thermostat wire
for lengths up to 100 ft. For wire lengths over 100 ft, use AWG
No. 16 wire.
NOTE:

For additional thermostat connection diagrams,

reference Fig. 52--59.
Accessories

1. Electronic Air Cleaner (EAC)

The furnace control EAC terminals are energized with
115v (1.0--amp maximum) during blower operation.
Connect an accessory Electronic Air Cleaner (if used)

using 1/4--in. female quick connect terminals to the two
male 1/4--in. quick--connect terminals on the control board

marked EAC--1 and EAC--2. The terminals are rated for
115VAC, 1.0 amps maximum and are energized during
blower motor operation. (See Fig. 33.)

NOTE: Low stage airflow may slightly increase the trace
amount of ozone created by an electronic air cleaner. Individual
sensitivity levels to ozone, along with other operating
characteristics of electronic air cleaners may affect the amount
noticed by an individual. Refer to the air cleaner manufacturer’s
installation instructions for more information regarding ozone
and ozone reduction methods available for your air cleaner.

UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component

damage.
DO NOT connect furnace control HUM terminal to HUM

(humidifier) terminal on Thermidistatt, Zone Controller or

similar device. See Thermidistatt, Zone Controller,

thermostat, or controller manufacturer’s instructions for

proper connection.

CAUTION

!

2. Humidifier (HUM)

Connect an accessory 24 VAC, 0.5 amp maximum

humidifier (if used) to the 1/4--in. male quick--connect
HUM terminal and COM--24V screw terminal on the

control board thermostat strip. The HUM terminal is
energized when blower is energized in heating. (See Fig.
33.)

355C

A

V

Advertising