Caution, Warning – Bryant Condensing Gas 355CAV User Manual

Page 33

Advertising
background image

33

COMBUSTION

AIR PIPE

BURNER

BOX

COMBUSTION AIR

INTAKE HOUSING

3/8" ID TUBE

TRAP

TO OPEN

DRAIN

3/16"

DRILL

4″

MIN

A93035

Fig. 40 -- Intake Housing Plug Fitting Drain

8. Install casing hole filler cap (factory--supplied in loose

parts bag) in unused combustion air pipe casing hole.

Attachment of Combustion Air Intake Housing Plug Fitting
The combustion--air intake plug fitting must be installed in
unused combustion air intake housing. This fitting must be

attached by using RTV sealant, or by drilling a 1/8--in. hole in
fitting, using hole in intake housing as a guide. Install a

field--supplied No. 6 or No. 8 sheet metal screw.
NOTE:

DO NOT OVERTIGHTEN SCREW. Breakage of

intake housing or fitting may cause air leakage to occur.
A plugged drain connection has been provided on this fitting for

use when moisture is found in combustion air intake pipe and
combustion box.
If use of this drain connection is desired, drill out fitting’s tap

plug with 3/16--in. drill and connect a field--supplied 3/8--in. tube.
This tube should be routed to open condensate drain for furnace

and A/C (if used), and should be trapped, as shown in Fig. 40.
NOTE:

(Direct Vent/2--Pipe System ONLY). Moisture in

combustion air intake may be a result of improper termination.
Ensure combustion air pipe termination is similar to those as
shown in Fig. 36 so that it will not be susceptible to area where
light snow or others sources of moisture could be pulled in.
Combustion Air Termination -- Ventilated Combustion Air
Option
Provisions for adequate combustion, ventilation, and dilution air
must be provided in accordance with:

S

U.S. Installations: Section 9.3 of the NFGC, Air for
Combustion and Ventilation and applicable provisions
of the local building codes.

S

Canadian Installations: Part 8 of CAN/CS--B149.1--05.
Venting Systems and Air Supply for Appliances and all
authorities having jurisdiction.

Combustion air is piped directly to the burner box on furnace
using the same materials used to vent the furnace. (See Table 5.)

The combustion air pipe is terminated in an attic or crawl space

that is well ventilated with OUTDOOR AIR and is well isolated
from the living space or garage. If the furnace is installed in a well

ventilated attic, crawlspace or other enclosure, the combustion air
pipe can be terminated in the same space.

UNIT CORROSION HAZARD
Failure to follow this caution may result in reduced furnace

component life.
Air for combustion must not be contaminated by halogen

compounds, which include fluoride, chloride, bromide, and

iodide. These elements may corrode heat exchangers and

shorten furnace life. Air contaminants are found in aerosol

sprays, detergents, bleaches, cleaning solvents, salts, air

fresheners, and other household products.

CAUTION

!

The combustion air pipe cannot be terminated in attics or

crawlspaces that use ventilation fans designed to operate during
the heating season. If ventilation fans are present in these areas,

the combustion air pipe must terminate outdoors as a Direct
Vent/2-- Pipe system.

CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal

injury or death.
The operation of exhaust fans, kitchen ventilation fans,

clothes dryers, attic exhaust fans or fireplaces could create a

NEGATIVE PRESSURE CONDITION at the furnace.

Makeup air MUST be provided for the ventilation devices,

in addition to that required by the furnace. Refer to the

Carbon Monoxide Poisoning Hazard warning at the end of

this section to determine if an adequate amount of make--up

air is available.

!

WARNING

NOTE: Combustion air pipe must have the same diameter as
vent pipe.
An attic or crawlspace may be considered a space that freely

communicates with the outdoors provided there are adequate
permanent ventilation openings directly to outdoors having free

area of at least 1--in.2/4,000 Btuh of total input rating for all gas

appliances in the space.
NOTE: In determining the free area of an opening, the blocking
effect of the louvers, grilles, and screens must be considered. If
the free area of a louver or grille design is unknown, it may be
assumed that wood louvers have a 20 percent free area, and metal
louvers or grilles have a 60 percent free area. Screens, when used,
must not be smaller than 1/4--in. mesh. Louvers and grilles must
be constructed so they cannot be closed.

CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal

injury or death.
Many homes require air to be supplied from outdoors for

furnace combustion, ventilation, and dilution of flue gases.
The furnace combustion air supply must be provided in

accordance with this instruction manual.

!

WARNING

Attic terminations require at least (1) 90 degree elbow, with the

open end pointing horizontally or downward. The open end of
the elbow must be at least 12--in. (304.8mm) above any

insulation or other materials. Screen the elbow with a wire mesh

screen no smaller than 3/8--inch square. (See Fig. 41.)

355C

A

V

Advertising