Fig. 16 -- Prohibit Installation on Back

UNIT DAMAGE HAZARD
This gas furnace may be used for construction heat

provided that:
--The furnace is permanently installed with all electrical

wiring, piping, air filters, venting and ducting installed

according to these installation instructions. A return air duct

is provided, sealed to the furnace casing, and terminated

outside the space containing the furnace. This prevents a

negative pressure condition as created by the circulating air

blower, causing a flame rollout and/or drawing combustion

products into the structure.

--The furnace is controlled by a thermostat. It may not be

“hot wired” to provide heat continuously to the structure

without thermostatic control.

--Clean outside air is provided for combustion. This is to

minimize the corrosive effects of adhesives, sealers and

other construction materials. It also prevents the

entrainment of drywall dust into combustion air, which can

cause fouling and plugging of furnace components.

--The temperature of the return air to the furnace is

maintained between 55_F (13_C) and 80_F (27_C), with

no evening setback or shutdown. The use of the furnace

while the structure is under construction is deemed to be

intermittent operation per our installation instructions.

--The air temperature rise is within the rated rise range on

the furnace rating plate, and the firing rate has been set to

the nameplate value.

--The filters used to clean the circulating air during the

construction process must be either changed or thoroughly

cleaned prior to occupancy.

--The furnace, ductwork and filters are cleaned as necessary

to remove drywall dust and construction debris from all

HVAC system components after construction is completed.

--After construction is complete, verify furnace operating

conditions including ignition, input rate, temperature rise

and venting, according to the manufacturer’s instructions.

CAUTION

!

FIRE OR DEATH HAZARD
Failure to follow this warning could result in property

damage, personal injury, or death.
Do not install furnace on its back. (See Fig. 16.) Safety

control operation will be adversely affected. Never connect

return--air ducts to back of furnace.

!

WARNING

The furnace and its return air system shall be designed and

installed so that negative pressure created by the air circulating
fan cannot affect another appliance’s combustion air supply or act

to mix products of combustion with circulating air, and that the
air circulating fan of the furnace, if installed in an enclosure

communicating with another fuel--burning appliance not of the
direct--vent type, shall be operable only when any door or panel

covering an opening in the furnace fan compartment or in a return

air plenum on ducts is in the closed position.

UNIT DAMAGE HAZARD
Failure to follow this caution may result in minor property

or unit damage.
If these furnaces are installed in an unconditioned space

where ambient temperatures may be 32_F (0_C) or lower,

freeze protection measures must be taken. See Condensate

Drain Protection section and Fig. 17.

CAUTION

!

32oF MINIMUM INSTALLED
AMBIENT OR FREEZE
PROTECTION REQUIRED

A93058

Fig. 17 -- Freeze Protection

Furnace Location Relative to Cooling Equipment
The cooling coil must be installed parallel with or on downstream

side of furnace to avoid condensation in heat exchanger. When

installed parallel with a furnace, dampers or other means used to
control flow of air shall be adequate to prevent chilled air from

entering furnace. If dampers are manually operated, they must be
equipped with a means to prevent operation of either unit unless

damper is in full--heat or full--cool position.