Bryant Condensing Gas 355CAV User Manual

Page 11

Advertising
background image

11

b. Remove and discard UPPER (molded) inducer housing

drain tube which was previously connected to condensate

trap.

CAP

PLUG

COLLECTOR BOX

DRAIN TUBE (BLUE &

WHITE STRIPED)

INDUCER HOUSING

(MOLDED) DRAIN

TUBE (VIOLET)

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

DRAIN TUBE (BLUE)

COLLECTOR BOX

TUBE EXTENSION

CONDENSATE

TRAP

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

EXTENSION

DRAIN TUBE

DRAIN TUBE

COUPLING

AUXILIARY “J” BOX

A07278

Fig. 11 -- Horizontal Left Tube Configuration

c. Install cap and clamp on UPPER inducer housing drain

conection where molded drain tube was removed.

d. Use inducer housing drain tube (violet label and

factory--supplied in loose parts bag) to connect LOWER
inducer housing drain connection to the condensate trap.

e. Connect inducer housing drain connection to condensate

trap.

(1.) Condensate Trap Located on Left Side of Casing

(a.)Determine appropriate length and cut.

(b.)connect tube to condensate trap.

(c.)Clamp tube to prevent any condensate leakage.

(2.) Condensate Trap Located on Right Side of Casing

(a.)Route inducer yhousing drain tube (violet label)

directly from inducer housing to condensate
trap.

(b.)Determine apprpriate length and cut.

(c.)Connect tube to condensate trap.

(d.)Clamp tube to prevent any condensate leakage.

3. Relief Port Tube

Refer to Pressure Switch Tubing section for connection
procedure.

Condensate Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and
procedures.
Pressure Switch Tubing
One collector box pressure tube (pink label) is factory connected

to the pressure switch for use when furnace is installed in
UPFLOW or HORIZONTAL LEFT applications.

The tube

MUST be disconnected and used or the condensate trap relief

port tube. The other collector box pressure tube (green label)

which was factory connected to the condensate trap relief port
connection MUST be connected to the pressure switch in

DOWNFLOW or HORIZONTAL RIGHT applications.
NOTE: See Fig. 9 or 10 or tube routing label on man furnace
door to check for proper connections.
Relocate tubes as described below.

1. Disconnect collector box pressure tube (pink label)

attached to pressure switch.

2. Extend collector box pressure tube (green label) which

was previously connected to condensate trap relief port
connection by splicing to small diameter tube

(factory--supplied in loose parts bag).

3. Connect collector box pressure tube (green label) to

pressure switch connection labeled COLLECTOR BOX.

4. Extend collector box pressure tube (pink label) which was

previously connected to pressure switch by splicing to

remaining small diameter tube (factory--supplied in loose
parts bag).

5. Route this extended tube (pink label) to condensate trap

relief port connection.

6. Determine appropriate length, cut, and connect tube.
7. Clamp tube to relief port connection.

Condensate Trap Freeze Protection
Refer

to

Condensate

Drain

Protection

section

for

recommendations and procedures.

HORIZONTAL LEFT (SUPPLY--AIR DISCHARGE)

APPLICATIONS

A horizontal left furnace application is where furnace blower is

located to the right of combustion and controls section of furnace,
and conditioned air is discharged to the left.

355C

A

V