Det-Tronics PIR9400 PointWatch Infrared Hydrocarbon Gas Detector User Manual

Page 15

Advertising
background image

13

95-8440

9.3

DETECTOR SEPaRaTION (OPTIONaL)
In applications where the detector must be installed in a

different location from the control device, a PIRTB must

be installed at the detector location to make the electrical
connection. The control device can be the FlexVu UD

10

,

Infiniti U

9500

Transmitter or the tall cover termination box

with window. Refer to Figure

21

for a typical separation

diagram. For purposes of brevity the following discussion
only refers to the Infiniti U

9500

Transmitter as the control

device.

By connecting a length of tubing (

1/4

inch O.D.) from the

direct inject calibration nozzle back to the control device

location, the operator can accomplish calibration from

the remote location.

Wiring Requirements for Detector Separation
Shielded four wire cable is recommended for connecting

the detector termination box to the transmitter. Cable with

a foil shield is recommended. The shield of the cable

should be open at the detector termination box and

connected to earth ground at the transmitter termination

box. Ensure that the shield wire is clipped short and

insulated with electrical tape to prevent accidental

grounding at the open end.

The maximum distance between the detector termination

box and the transmitter is limited by the resistance of the

connecting wiring, which is a function of the gauge of
the wire being used. Refer to Figure

2

to determine the

maximum separation distance for a given wire size.

NOTE

It is important to maintain a minimum of

+18

Vdc

(including ripple) at the PointWatch Detector.
When determining the appropriate wire size for the
installation, refer to Figure

2

. Be sure to take into

account the distance from the power supply to the
PointWatch Detector or to the U

9500

Transmitter

and then to the PointWatch Detector to ensure that
the power requirements are met.

+

24 VDC

POWER SUPPLY

4 TO 20 MILLIAMPERES

INFINITI TRANSMITTER

PIRTB TERMINATION BOX

CHASSIS

+

+

PO
WER OUT

NO

COM

NC

NO

COM

NC

NO

COM

A

UX RELA

Y

LO

W RELA

Y

HIGH RELA

Y

NC

NO
COM

NC

S


+

S

+
+

RESET

CA
L

FA

UL

T RELA

Y

PO
WER

PW

IN

A1737

SPARE

CAL

4 – 20

RET

+

24

CHASSIS

CAL

4 – 20

RET

+

24

POINTWATCH

DETECTOR

GREEN
YELLOW
WHITE
BLACK
RED

Figure 22—Sensor Separation with Infiniti U9500 Transmitter and PIR9400

TERMINATION BOX

POINTWATCH

DETECTOR

SUITABLE WIRING.

MUST MEET ALL LOCAL CODES.

CONTROL DEVICE SUCH AS INFINITI TRANSMITTER,

FLEXVU UD10, OR TALL COVER JUNCTION BOX WITH WINDOW

C1757

Figure 21—Options for Detector Separation

Advertising