Appendix b, Csa approval – Det-Tronics PIR9400 PointWatch Infrared Hydrocarbon Gas Detector User Manual

Page 29

Advertising
background image

27

95-8440

9.3

APPENDIX B

CSa aPPROVaL

The following items, functions and options describe the CSA approval.

aPPROVaL
PointWatch Infrared Hydrocarbon Gas Detector Model PIR

9400

Series.

Explosion-proof for Class I, Division

1

, Groups B, C, & D (T

5

) Hazardous (Classified) Locations per C

22.2 #30

.

Nonincendive for Class I, Division

2

, Groups A, B, C & D (T

3

C) Hazardous (Classified) Locations per C

22.2 #213

.

Performance verified for

0

to

100%

LFL Methane-in-air atmospheres per C

22.2 #152

.

NOTE

Model PIR

9400

must be used in conjunction with an CSA Approved control device.

PointWatch Termination Box Model PIRTB Part Number

006414

-XXX.

Explosion-proof for Class I, Division

1

, Groups B, C, & D (T

6

) Hazardous (Classified) Locations per C

22.2 #30

.

Nonincendive for Class I, Division

2

, Groups A, B, C & D (T

6

) Hazardous (Classified) Locations per C

22.2 #213

.

NOTE

Approval of the PointWatch Detector and termination box does not include or imply approval of the apparatus to
which the PointWatch Detector may be connected and which processes the electronic signal for eventual end
use.

Special Conditions of Use:

1. Approval covers us of the instruments when calibration is performed using the gas to be monitored and the highest

alarm set points are preset within

10%

of the calibration gas concentration.

2. The apparatus may be used with CSA Approved PointWatch Termination Box Model PIRTB Series.

aTTaChMENTS/OPTIONS
Aluminum or Stainless Steel Explosion-proof Enclosure, with Aluminum or Plastic Baffle.

3/4

inch NPT and M

20

Conduit Entry Thread Types. (Metric straight thread is for use in non-North American

applications.)
Calibration Kit (

006468

-xxx)

50%

LFL Calibration Gas (

226166

-xxx)

Calibration Nozzle (

102821-001

)

Regulator (

162552

-xxx)

Tubing (

101678-007

).

CaLIBRaTION
The PointWatch Model PIR

9400

can be calibrated as a stand-alone point gas detector.

PointWatch Termination Box Model PIRTB (

006414

-xxx) can be used to calibrate the PointWatch Detector.

NOTE

It is required that calibration of PointWatch Detector be conducted as well as calibration of the system in which it
is installed.

Advertising