Appendix c, Atex / ce approval – Det-Tronics PIR9400 PointWatch Infrared Hydrocarbon Gas Detector User Manual

Page 30

Advertising
background image

28

95-8440

9.3

APPENDIX C

aTEx / CE aPPROVaL

aTEx CERTIFICaTION

PointWatch Detector Model PIR

9400

0539

FM

APPROVED

®

II

2

G

Ex d

II

B + H

2

T

4

-T

6

Gb

EN

60079-29-1

DEMKO

09

ATEX

147301

X

T

6

(Tamb = –

55°

C to +

50°

C)

T

5

(Tamb = –

55°

C to +

60°

C)

T

4

(Tamb = –

55°

C to +

75°

C)

IP

66

.

EN Standards: EN

50270: 2006

EN

60079-0: 2009

EN

60079-1: 2007

EN

60529: 1991+

A

1: 2000

EN

60079-29-1: 2007.

Read and understand instruction manual before operating.

Special Conditions for Safe Use:

The Gas Detectors have a threaded wire feed through incorporating flying leads. This feed through is to be

screwed into the cable entry opening of a suitable ATEX certified (Ex ‘d’ or Ex ‘e’) enclosure in which the flying

leads are to be terminated.

In order to maintain the Ingress Protection rating IP

66

, the back end of the PointWatch Infrared Hydrocarbon

Gas Detector Model PIR

9400

with the flying lead is to be screwed into a suitable ATEX certified (Ex ‘d’ or Ex ‘e’)

enclosure with an Ingress Protection rating of at least IP

66

.

The PointWatch Infrared Hydrocarbon Gas Detector Model PIR

9400

has an ambient temperature rating for

performance of –

55°

C to +

75°

C.

The PointWatch Infrared Hydrocarbon Gas Detector Model PIR

9400

is to be used only in conjunction with a suitable

ATEX certified combustible gas detector control unit for compliance with EN

60079-29-1

standard.

The captive front-end screws are to be tightened with

1

N·m.

Performance Testing to EN

60079-29-1

The measuring function of the Model PIR

9400

Gas Detector, according to Annex II paragraph

1.5.5, 1.5.6

and

1.5.7

of the Directive

94/9/

EC, is covered in this Type Examination Certificate in the following configuration:

1

. Sensor Termination Box (STB) and Calibration Termination Box (CTB), in combination with Det-Tronics gas

detector model PIR

9400

(tested with methane applied to the PIR

9400

), firmware

005998-005

Rev F.

CE MaRk
The PointWatch Infrared Hydrocarbon Gas Detector Model PIR

9400

was tested and found to be compliant with

EN

50270

when wired in conduit or with shielded cable. All screen drains shall be terminated to the chassis.

Advertising