Appendix a, Fm approval – Det-Tronics PIR9400 PointWatch Infrared Hydrocarbon Gas Detector User Manual

Page 28

Advertising
background image

26

95-8440

9.3

APPENDIX A

FM aPPROVaL

The following items, functions and options describe the FM approval.

aPPROVaL
PointWatch Infrared Hydrocarbon Gas Detector Model PIR

9400

Series.

Explosion-proof for Class I, Division

1

, Groups B, C, & D (T

5

) Hazardous (Classified) Locations per FM

3615

.

Nonincendive for Class I, Division

2

, Groups A, B, C & D (T

3

C) Hazardous (Classified) Locations per FM

3611

.

Performance verified for

0

to

100%

LFL Methane-in-air atmospheres per FM

6320

, ANSI/ISA

12.13.01-2000

.

NOTE

Model PIR

9400

must be used in conjunction with an FM Approved control device.

PointWatch Termination Box Model PIRTB Part Number

006414

-XXX.

Explosion-proof for Class I, Division

1

, Groups B, C, & D (T

6

) Hazardous (Classified) Locations per FM

3615

.

Non-incendive for Class I, Division

2

, Groups A, B, C & D (T

6

) Hazardous (Classified) Locations per FM

3611

.

NOTE

Approval of the PointWatch Detector and termination box does not include or imply approval of the apparatus to
which the PointWatch Detector may be connected and which processes the electronic signal for eventual end
use.

Special Conditions of Use

:

1. Approval covers us of the instruments when calibration is performed using the gas to be monitored and the highest

alarm set points are preset within

10%

of the calibration gas concentration.

2. The apparatus may be used with FM Approved PointWatch Termination Box Model PIRTB Series.

aTTaChMENTS/OPTIONS
Aluminum or Stainless Steel Explosion-proof Enclosure, with Aluminum or Plastic Baffle.

3/4

inch NPT and M

20

Conduit Entry Thread Types. (Metric straight thread is for use in non-North American

applications.)
Calibration Kit (

006468

-xxx)

50%

LFL Calibration Gas (

226166

-xxx)

Calibration Nozzle (

102821-001

)

Regulator

(162552

-xxx)

Tubing (

101678-007

).

CaLIBRaTION
The PointWatch Model PIR

9400

can be calibrated as a stand-alone point gas detector.

PointWatch Termination Box Model PIRTB (

006414

-xxx) can be used to calibrate the PointWatch Detector.

NOTE

It is required that calibration of the PointWatch Detector be conducted as well as calibration of the system in
which it is installed.

Advertising