1

95-8440

9.3

Caution

Be sure to read and understand the entire
instruction manual before installing or operating
the gas detection system. This product is intended
to provide early warning of the presence of a
flammable or explosive gas mixture. Proper device
installation, operation, and maintenance is required
to ensure safe and effective operation. If this
equipment is used in a manner not specified in
this manual, safety protection may be impaired.

APPLICATION

The PointWatch

TM

Infrared Gas Detector Model PIR

9400

is a diffusion-based point-type infrared gas detector. The

PointWatch Detector is approved to provide continuous

monitoring of methane gas concentration in the range of

0

to

100%

LFL. The detector provides a

4-20

mA output

signal, corresponding to the detected gas concentration.

It has Division and Zone explosion-proof ratings and is

suitable for use in indoor and outdoor applications.

The PointWatch Detector Model PIR

9400

is ideally suited

for use in harsh environments and where the cost of

required maintenance for conventional catalytic detectors

is prohibitive. It will perform reliably in the presence of

silicone and other catalytic poisoning agents and can

also operate in oxygen free environments or where high

background gas levels are present. There are no known

poisons that affect this technology.

The PointWatch Detector is globally certified for use
in Class

1

, Divisions

1

and

2

, and Zone

1

hazardous

areas. It is also approved as a stand alone gas detector,

and complies with global approvals when connected

to a stand-alone approved controller for life safety.

The approved Det-Tronics controllers are the FlexVu

®

UD

10

, Infiniti

®

U

9500

, R

8471

, and Eagle Quantum

Premier

®

(EQP).

FEATURES

• Compliance to ANSI/ISA

12.13.01-2000

performance

standard.

• Requires no routine calibration to ensure proper

operation.

• Fail-safe operation.
• Continuous self-test automatically indicates a fault

or fouled optics condition.

• Unique multi-layered filtering system protects

optics from dirt and water ingress.

• Internal heating system minimizes condensation,

allowing reliable operation through temperature

extremes.

• There are no known poisons, e.g. silicones or

hydrides, that compromise the integrity of the

measurement.

• Performs well in the presence of high concentrations

or constant background levels of hydrocarbons,

and in oxygen depleted atmospheres.

• Standard

4–20

mA output (current source).

• Compact, lightweight, explosion-proof housing is

designed for duty in harsh environments.

• Standard

0

to

100%

LFL detection range.

INSTRUCTIONS

PointWatch

TM

Infrared

Hydrocarbon Gas Detector

Model PIR

9400

©

Detector Electronics Corporation 2012

Rev: 11/12