Iv. control system specifications, Iv. c, Ontrol – Elkhart Brass Stinger RF8297 User Manual
Page 13: Ystem, Pecifications
10
IV. C
ONTROL
S
YSTEM
S
PECIFICATIONS
Handheld Transmitter Specifications
Input power
2 AA batteries (Alkaline recommended)
Output power
Meets FCC part 15 requirements for license free
operation
Transmitter dimensions
6” x 3 1/4” x 1 3/8”
Transmitter weight
10 ½ oz.
Operating temperature range
-40
F to 150
F (-40
C to 65
C)
FCC ID
QT8PTSS2011
Transmitter Specifications
Input power
12/24 VDC (11VDC to 30 VDC)
Output power
Meets FCC part 15 requirements for license free
operation
Transmitter dimensions
7 5/8” x 3 7/8” x 2 3/8”
Operating temperature range
-40
F to 150
F (-40
C to 65
C)
FCC ID
QT8PTSS2011
Receiver Specifications
Power requirements
12VDC (11VDC to 14VDC) at the controller under full
load
Control current
0.07 A
*
Operating temperature range
-40
F to 150
F (-40
C to 65
C)
Table 1
Motor Current Specifications
Monitor
Left/Right
Up/Down
Nozzle
Run
2.5 A
2.5 A
0.5 A
Stall
12 A
12 A
NA
Current Trip Point
9 A
9 A
4 A
Shock:
30 G's (55 Hz. @ .2 inch double amplitude)
Vibration:
15.5 G's (55 Hz. @ .05 inch double amplitude) continuous operation
Drop Test:
The handheld transmitter must meet operating specifications after drop from 1-meter height onto
concrete surface.
Environmental:
All enclosures have a NEMA 4 rating (must withstand a 1 inch stream of water (65 gpm) from a distance of
ten feet for five minutes, with no water entering the enclosure
*
All current ratings are at 12 volts