Iv. control system specifications, Iv. c, Ontrol – Elkhart Brass Stinger RF8297 User Manual

Page 13: Ystem, Pecifications

Advertising
background image

10

IV. C

ONTROL

S

YSTEM

S

PECIFICATIONS

Handheld Transmitter Specifications

Input power

2 AA batteries (Alkaline recommended)

Output power

Meets FCC part 15 requirements for license free
operation

Transmitter dimensions

6” x 3 1/4” x 1 3/8”

Transmitter weight

10 ½ oz.

Operating temperature range

-40

F to 150

F (-40

C to 65

C)

FCC ID

QT8PTSS2011

Transmitter Specifications

Input power

12/24 VDC (11VDC to 30 VDC)

Output power

Meets FCC part 15 requirements for license free
operation

Transmitter dimensions

7 5/8” x 3 7/8” x 2 3/8”

Operating temperature range

-40

F to 150

F (-40

C to 65

C)

FCC ID

QT8PTSS2011

Receiver Specifications

Power requirements

12VDC (11VDC to 14VDC) at the controller under full
load

Control current

0.07 A

*

Operating temperature range

-40

F to 150

F (-40

C to 65

C)

Table 1

Motor Current Specifications

Monitor

Left/Right

Up/Down

Nozzle

Run

2.5 A

2.5 A

0.5 A

Stall

12 A

12 A

NA

Current Trip Point

9 A

9 A

4 A

Shock:

30 G's (55 Hz. @ .2 inch double amplitude)

Vibration:

15.5 G's (55 Hz. @ .05 inch double amplitude) continuous operation

Drop Test:

The handheld transmitter must meet operating specifications after drop from 1-meter height onto
concrete surface.

Environmental:

All enclosures have a NEMA 4 rating (must withstand a 1 inch stream of water (65 gpm) from a distance of
ten feet for five minutes, with no water entering the enclosure

*

All current ratings are at 12 volts