Requirements for connection cables – EUCHNER CETx-AR-xxx-AH-xxx (Unicode) User Manual

Page 19

Advertising
background image

Operating Instructions Safety Switch CET.-AR-...-AH-...

19

Requirements for connection cables

Caution!

Risk of damage to equipment or malfunctions as a result of incorrect connec-
tion cables.

 Ì

Use connection components and connection cables from EUCHNER

 Ì

On the usage of other connection components, the requirements in the fol-
lowing table apply. EUCHNER provides no warranty for safe function in case 
of failure to comply with these requirements. 

Observe the following requirements with respect to the connection cables:
For safety switch CET-AR with plug connectors 2 x M12

Parameter

Value

Unit

Wire cross-section min.

0.34

mm²

R max.

60

W/km

C max.

120

nF/km

L max.

0.65

mH/km

Recommended cable type

LIYY 8x or 5x 0.34 mm²

For safety switches CET-AR with plug connector RC18

Parameter

Value

Unit

Wire cross-section min.

0.34

mm²

R max.

60

W/km

C max.

120

nF/km

L max.

0.65

mH/km

Recommended cable type

LIFY11Y min. 19-cores