8 quick stop, Quick stop (c 22), 9400 technology applications | actuator – torque – Lenze E94AxHE Technology Application Actuating drive - Torque User Manual

Page 22: Parameter setting & configuration quick stop

Advertising
background image

9400 Technology applications | Actuator – torque

Parameter setting & configuration

Quick stop

22

L

EDS94TA10020xxxx EN 1.1 - 10/2008

4.8

Quick stop

[4-10] Basic function "Quick stop" (schematic diagram)

r

The quick stop function can be activated as follows in the Lenze setting:
– By setting the digital input DI1 to LOW level.
– By a master control via the port LPortAxisIn1:

By setting bit 3 of the bit-coded axis control word.

r

Parameter setting: Application parameters tab  dialog level Overview  Quick stop

The basic function "Quick stop" brakes the

drive to standstill within the deceleration

time set for the quick stop function after a

corresponding request independent of the

setpoint selection.
If the quick stop is deactivated, the defined

torque is available again, as the case may

be, an acceleration via the set acceleration

time of the speed limit value is effected.

LS_ManualJog

n

t

и

з

LS_Brake

n

t

LS_Limiter

n

t

LS_Quickstop

STOP

LS_Torque...

M

Torque
setpoint

n

t

LS_Stop

internal
status machine

DI2

DI6

DI7
DI8

DI1

Status

machine

(basic drive

functions)

Basic drive functions

M

v

F

и
з

Parameter

Lenze setting

Value Unit

C00105

Quick stop deceleration time

0.000 s

C00106

Quick stop S-ramp time

0.00 %

C00107

Reference for quick stop deceleration time

Motor reference speed (C00011)

Control inputs of the function

Signal configuration

Lenze setting

Control input

(Multiplexer parameters)

DIGIN 1  Activate quick stop 1

C03135/1

Axis control word

bit 03



Activate quick stop 2

C03135/2

FALSE  Activate quick stop 3

C03135/3

Advertising