Insulation of piping – Roxul Industrial Insulation Process User Manual

Page 32

Advertising
background image

Insulation of piping

1.2.1 Insulation with pipe sections

Generally, the best insulation is achieved using
ProRox

®

Pipe Sections. The sections can be used

up to temperatures of 1400 °F (760 °C) when
using ProRox

®

PS 980

NA

Type V insulation. They

are supplied ready split and hinged for quick
and easy snap-on assembly and are suitable for
thermal and acoustic insulation of industrial pipe
work. Their excellent fit and high compression
resistance means pipe sections can be applied
in a single layer without any additional spacers
or support structures. Consequently the number
of thermal bridges, which have a negative
influence on the insulation, is greatly reduced,
while a low thickness may be applied compared
to wired mats. The result is considerably reduced
installation time and costs. The lack of spacers
and “unforeseen” gaps minimizes heat loss and
the risk of personnel injuries due to hot spots on
the cladding.

At temperatures above 550 °F (300 °C), the
provisional application of spacers must be
determined in each individual case. ProRox

®

Pipe Sections are available in a wide range of
diameters, ranging from NPS 1/2" (23 mm) to
36" (914 mm)

Note
Due to their low thermal conductivity, better
thermal insulation values can be achieved
with pipe sections than with wired mats.
With insulation on straight pipe sections, a
combination of both products in the same
insulation thickness is therefore not advisable.
If this combination is essential, for example,
in the case of bends or shaped pieces, it is
vital to select the correct insulation thickness.
This is the only way to guarantee that no
unexpected, potentially hazardous surface
temperatures occur.

Insulation thicknesses to guarantee

protection against contact

The table below is an initial guide to help select
suitable insulation thicknesses for the guards.
It is based on the following boundary conditions:

Ambient temperature: 75 °F (25 °C)

Wind speed: 1.1 mph (0.5 m/s)

Cladding: Aluminum

Maximum surface temperature: 140 °F (60 °C)

Insulation: ProRox

®

PS 960

NA

pipe sections

Pipe Diameter

Temperature

NPS

(inch)

Nominal

diameter

Ø DN

Pipe

diameter

(mm)

<250 °F

(<120 °C)

300 °F

(150 °C)

350 °F

(175 °C)

400 °F

(200 °C)

450 °F

(230 °C)

500 °F

(260 °C)

550 °F

(290 °C)

600 °F

(315 °C)

inch

inch

inch

inch

inch

inch

inch

inch

1

25

33

0.5"

0.5"

0.5"

0.5"

1"

1"

1"

1"

2

50

60

0.5"

0.5"

0.5"

1"

1"

1"

1.5"

1.5"

3

80

89

0.5"

0.5"

1"

1"

1"

1.5"

1.5"

2"

4

100

114

0.5"

0.5"

1"

1"

1"

1.5"

1.5"

2"

6

150

168

0.5"

1"

1"

1"

1.5"

1.5"

2"

2"

8

200

219

0.5"

1"

1"

1.5"

1.5"

1.5"

2"

2.5"

10

250

273

0.5"

1"

1"

1.5"

1.5"

2"

2"

2.5"

12

300

324

0.5"

1"

1"

1.5"

1.5"

2"

2"

2.5"

The thicknesses mentioned above should be seen as an indication. In the event of differing boundary conditions, please
contact the ROXUL

®

Technical Services Team. The thermo-technical engineering program "ROCKASSIST" (coming soon)

or NAIMA 3E Plus

®

can be used to design the insulation according to the specific requirements.

29

Advertising