Insulation of c

olumns

1. Support construction - 2. Mounting support -
3. Reinforcement ring - 4. ProRox

®

insulation -

5. Cladding

In a wide variety of applications, these values can
only be used as reference values. In each
individual case, determine whether different strap
measurements and intervals should be used. If
the insulation is assembled in multiple layers,
the joints of the individual insulation layers must
be staggered. The following illustrations show a
number of typical methods of insulating columns.

External insulation

diameter

Internal insulation layer strap

measurement

External or single layer insulation

strap measurement

Distance between

the straps

8" to 72" (200 to 1800 mm)

1/2" x 0.02" (13 x 0.5 mm)

5/8" x 0.02" (16 x 0.5 mm)

10" (250 mm)

> 72" (1800 mm)

5/8" x 0.02" (16 x 0.5 mm)

3/4" x 0.02" (19 x 0.5 mm)

10" (250 mm)

2"

(50 mm

)

Insulation of conical column head

1. Supporting construction - 2. Mounting support

Insulation of a reinforcement ring

55