Installation, Combustible mantels – Regency Panorama P33E Small Gas Fireplace User Manual

Page 11

Advertising
background image

Regency® P33E-4 Zero Clearance Direct Vent Gas Fireplace

11

INSTALLATION

COMBUSTIBLE MANTELS

Because of the extreme heat this fi replace emits, the mantel clearances are critical. Combustible mantel clearances from top of unit are
shown in the diagram below.

Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible

board.

This drawing is to scale at 1:6 (one inch = 6 inches). Mantel can be installed anywhere in shaded area or higher using the above scale.

Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the paint may discolour.

Combustible mantel leg clearances as per diagrams below:

Drywall

Mantel Clearances

with Flush, Full Screens or Bay Glass

2

0

12

6

4

8

10

2

0

12

6

4

8

10

Side View

Top of
Unit

12" (305mm)

0” - 3-1/2" (89mm)

7-1/2"(191mm)

11"(279mm)

7"(178mm)

9"(229mm)

29"(737mm)

to floor

3"(76mm)

Standof

f

Mantel Clearances with

Contemporary Faceplate