Installation, Framing and finishing – Regency Panorama P33E Small Gas Fireplace User Manual

Page 13

Advertising
background image

Regency® P33E-4 Zero Clearance Direct Vent Gas Fireplace

13

INSTALLATION

3) For exterior walls, insulate the enclosure to

the same degree as the rest of the house,
apply vapour barrier and drywall, as per
local installation codes. (Do not insulate
the fi replace itself.)

4) The top of the unit must not be closer than

30" (762mm) to the ceiling.

5) Combustible material may be brought up to

the top and sides of the unit and be covered
with ceramic tiles, bricks, rock or other
suitable combustible fi nishing materials.

Note: The unit does not have to be completely

enclosed in a chase. The clearance on
top of the unit is 0" to the standoffs so
combustible building materials can be
laid directly on top of the standoffs.
You must maintain clearance from
the vent to combustible materials
for fl ex or for Rigid Vent (Refer to
"Clearances" Section).

1) Determine the total thickness of facing

material (e.g. drywall plus ceramic tiles) to
allow the fi nished surface to be fl ush with
the front of the unit. Total facing thickness
can vary from 1/2" (13mm) to 1-1/4" (32mm)
thick.

6) Use steel studs for framing where the

1-1/2" (38mm) clearance from the vent
to combustible material cannot be
maintained.

2) Frame in the enclosure for the unit with

framing material.

FRAMING AND FINISHING

16-1/2”

(419mm)
Minimum

4"

(102mm)

3"

(76mm)

1-1/2"

(38mm)

30”

(762mm)

10" (254mm)

dia. Hole through

wall for Dura-Vent

1/2"
(13mm)
Drywall

Top Header

Opening for gas

connection

12-3/4”

(324mm)
Minimum

4"

(102mm)

3"

(76mm)

1-1/2"

(38mm)

26”

(660mm)

10" (254mm)

dia. Hole through

wall for Flex

1/2"
(13mm)
Drywall

Top Header

Opening for gas

connection

Rigid Vent

Minimum Clearances

Flex Vent

Minimum Clearances

Vertical Termination or

Vertical Rise with Horizontal

Termination

NOTE: If this is an outside corner, the
minimum distance between the vent and the
outside corner is 6" (15cm) with AstroCap
termination cap or 12" (30cm) with Rigid Vent
termination cap. (For example Dura-Vent).

For Both Rigid & Flex

Rear Termination

NOTE: If this is an outside corner, the minimum
distance between the vent and the outside
corner is 6" (15cm) with AstroCap termination
cap or 12" (30cm) with Rigid Vent termination
cap. (For Example Dura-Vent).

For Rigid Vent

For Flex Vent

For Both Rigid & Flex

The HeatWave Duct Kit has different
clearance and framing requirements,
check the HeatWave manual for details.

NOTE: Framing is different when using the
faceplate option.
See framing section when using faceplate in
this manual.

Install Side Nailing Strips, and Top Facing
Support before unit is slipped into position.
See "Unit Assembly Prior to Installation"
Section

Advertising