Installation, Fpi direct vent system (flex), Propane & natural gas) – Regency Panorama P36E Medium Gas Fireplace User Manual

Page 24

Advertising
background image

P36E-4 Zero Clearance Direct Vent Gas Fireplace

24

RIGID PIPE VENTING ARRANGEMENTS

HORIZONTAL TERMINATIONS

FPI DIRECT VENT SYSTEM (FLEX)

(Propane & Natural Gas)

The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90

o

elbow (two 45

o

elbows equal one 90

o

elbow).

Note: Must use optional rigid pipe adaptor (Part # 510-994) when using Rigid Pipe venting systems.

All Rigid Pipe Systems
4" inner diameter
6-5/8" outer diameter

FPI Flex Vent
4" inner diameter
6-7/8" inner diameter

• Maintain clearances to combustibles.
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each fl oor level and whenever passing through a wall.

NOTE: If you are installing the P36E into a FPI Cabinet Mantel Kit, use the minimum horizontal vent height (centre-line of 40-1/2").

Remember to include the mantel base (3" in height) in your calculations and to maintain the 2" clearance with rigid pipe and fl ex
systems to the underside of the mantel top.

A vent guard should be used
whenever the termination is lower
than the specifi ed minimum or as
per local codes.

Note: FPI

Direct Vent System (Flex

Part #'s 946-515, 946-516) is
only approved for horizontal
terminations.

INSTALLATION