Setting up network communications, Psw2, Comm – Titus Sensor STE-8001 and STE-8201 User Manual

Page 15: D id, Baud

Advertising
background image

STE-8001 and STE-8201 sensors

Revision A

Commissioning functions

Setting up network communications

15

Setting up
network
communications

Set the network communication settings before placing a controller on the
network. Setting network settings requires entering the Level 2 password which
is described in the topic

Enter the commissioning mode on page 14

.

Procedure to set up network communications

Procedure

Steps

STE display

Starting display

1. Start at the temperature display.

2. Enter the Level 2 password. The

display changes to the COMM.

Select the COMM
display

Press the button. The display changes
to DI D.

Enter the device
instance.

1. Press the or buttons to change

the first digit.

2. Press the button to select the next

digit. Repeat for all seven digits.

3. When the button is pressed for the

last digit, the display changes to MAC.

Enter the MAC
address.

1. Press the or buttons to change

the MAC address.

2. Press the button to save the

selected MAC address.
The display changes to BAUD.

Enter the baud

1. Press the or buttons to select a

new baud.

2. Press the button is save the

selected baud.
The display returns to COMM.

Advance or exit

1. Press the or buttons to select

one of the following:

BLNC

or

CNFG

options

EXIT

to return to the temperature

display.

2. Press the button to select the next

function.

72

12S1

PSW2

OOOO

Set

Point

COMM

Set

Point

Set

Point

D ID

OO72O69

Set

Point

MAC

11

Set

Point

BAUD

384OO

Set

Point

COMM