STE-8001 and STE-8201 sensors

Revision A

Commissioning functions

Setting the airflow setpoints

23

Setting the
airflow setpoints

The airflow setpoints configure the airflow limits for the VAV terminal unit.
Setting the airflow setpoints requires entering a Level 2 password which is
described in the topic

Enter the commissioning mode on page 14

.

Note

If the VAV unit is a heat only or cooling only unit, the airflow setpoints for the
unused mode must be set within the range of the mode in use. Failure to set the
unused setpoints correctly will result in unpredictable or erroneous air
balancing settings.

Procedure to set the airflow setpoints

Procedure

Steps

STE display

Starting display

1. Start at the temperature display.

2. Enter the Level 2 password. The

display changes to the COMM.

Select the flow
setpoint display.

1. From the COMM display, press the

or buttons to show the CNFG
display.

2. Press the button to select the CNFG

options. The display changes to

STPT.

3. Press the or buttons to change

the display to FLOW.

4. Press the button to select FLOW.

72

12S1

PSW2

OOOO

Set

Point

Set

Point

COMM

CNFG

STPT

FLOW