Mnc2, Mxc2, Flow – Titus Sensor STE-8001 and STE-8201 User Manual

Page 26

Advertising
background image

KMC Controls

Revision A

Commissioning functions
Setting the airflow setpoints

26

Set the minimum
limit for indoor air
quality ventilation

1. Press the or buttons to set the

minimum limit for ventilation
airflow. The setpoint will change in 1
CFM increments.

2. Press the button to save the

setpoint and advance to the next
function.

Set the maximum
limit for indoor air
quality ventilation

1. Press the or buttons to set the

maximum limit for ventilation
airflow. The setpoint will change in
1 CFM increments.

2. Press the button to save the

setpoint and advance to the next
function.

Advance or exit

1. Press the or buttons to select

one of the following:

STPT

,

BOX

, or

ADVC

options

BACK

to choose another

commissioning function

EXIT

to return to the temperature

display.

2. Press the button to select the next

function.

Procedure to set the airflow setpoints (Continued)

Procedure

Steps

STE display

Set

Point

OO

MNC2

Set

Point

3SO

MXC2

Set

Point

FLOW