Mncl, Mxcl, Mnht – Titus Sensor STE-8001 and STE-8201 User Manual

Page 25: Mxht

Advertising
background image

STE-8001 and STE-8201 sensors

Revision A

Commissioning functions

Setting the airflow setpoints

25

Set the cooling
minimum airflow
limit

1. Press the or buttons to set the

minimum limit for cooling airflow.
The setpoint will change in 1 CFM
increments.

2. Press the button to save the

setpoint and advance to the next
function.

Set the cooling
maximum airflow
limit

1. Press the or buttons to set the

maximum limit for cooling airflow.
The setpoint will change in 1 CFM
increments.

2. Press the button to save the

setpoint and advance to the next
function.

Set the heating
minimum airflow
limit

1. Press the or buttons to set the

minimum limit for heating airflow.
The setpoint will change in 1 CFM
increments.

2. Press the button to save the

setpoint and advance to the next
function.

Set the heating
maximum airflow
limit

1. Press the or buttons to set the

maximum limit for heating airflow.
The setpoint will change in 1 CFM
increments.

2. Press the button to save the

setpoint and advance to the next
function.

Set the minimum
limit for fan speed

1. Press the or buttons to set the

minimum limit for the fan speed. The
setpoint will change in 1%
increments.

2. Press the button to save the

setpoint and advance to the next
function.

Set the maximum
limit for fan speed

1. Press the or buttons to set the

maximum limit for the fan speed.
The setpoint will change in 1%
increments.

2. Press the button to save the

setpoint and advance to the next
function.

Procedure to set the airflow setpoints (Continued)

Procedure

Steps

STE display

Set

Point

OO

MNCL

Set

Point

3SO

MXCL

Set

Point

OO

MNHT

Set

Point

3SO

MXHT

Set

Point

2O

MIN

Set

Point

1OO

MAX

Advertising