Reht – Titus Sensor STE-8001 and STE-8201 User Manual

Page 17

Advertising
background image

STE-8001 and STE-8201 sensors

Revision A

Commissioning functions

Box options

17

Set the mode of
reheat for the
terminal unit

1. Press the or buttons to choose

one of the following reheat options.

None

—Reheat is not enabled.

Staged

—Enables two or three stage

reheat. If lighting is enabled the
staged reheat is set to two stages. If
lighting is not enabled, three reheat
stages are available.

Modulating

—The reheat output

varies from 0-10 volts.
Floating

—The reheat outputs control

a tristate actuator.
Time proportional

—Controls a

thermal wax valve with a 24-volt
triac output.

2. Press the button to save the reheat

option and advance to the next
function.

Set the fan option

1. Press the or buttons to choose

one of the following fan options.

None

—No fan is connected to the

controller.

Series

—The VAV unit includes a

series fan.

Parallel

—The VAV unit includes a

parallel fan.

2. Press the button to save the fan

option and advance to the next
function.

Procedure to set the box functions (Continued)

Procedure

Steps

STE display

Set

Point

NONE

REHT

Set

Point

NONE

FAN