Setting commissioning setpoints, Psw2, Comm cnfg stpt – Titus Sensor STE-8001 and STE-8201 User Manual

Page 20

Advertising
background image

KMC Controls

Revision A

Commissioning functions
Setting commissioning setpoints

20

Setting
commissioning
setpoints

The commissioning setpoints set the operational parameters and limits for the
VAV terminal unit. Setting configuration setpoints requires entering a Level 2
password which is described in the topic

Enter the commissioning mode on

page 14

.

Procedure to set the commissioning setpoints

Procedure

Steps

STE display

Starting display

Enter the Level 2 password. The display
changes to the COMM.

Select the setpoint
display.

1. From the COMM display, press the

or buttons to show the CNFG
display.

2. Press the button to select the CNFG

options. The display changes to

STPT.

3. Press the button to select the STPT

options.

Set the minimum
cooling setpoint

1. Press the or buttons to set the

minimum cooling setpoint. The
setpoint will change in 0.5°
increments.

2. Press the button to save the

setpoint and advance to the next
function.

Set the maximum
heating setpoint

1. Press the or buttons to set the

maximum heating setpoint. The
setpoint will change in 0.5°
increments.

2. Press the button to save the

setpoint and advance to the next
function.

PSW2

OOOO

Set

Point

Set

Point

COMM

CNFG

STPT

Set

Point

MIN

68O

Set

Point

MAX

78O