STE-8001 and STE-8201 sensors

Revision A

Commissioning functions

Balancing airflow

29

Advance or exit

1. Press the or buttons to select

one of the following:

SEC

to balance the secondary VAV

for dual duct systems

BACK

to choose another

commissioning function

EXIT

to return to the temperature

display.

2. Press the button to select the next

function.

Measure and enter
the actual
maximum
secondary airflow

The display begins flashing SMAX
and also displays the actual airflow
at the bottom.

Note:

The airflow displayed by the

STE-8000 in this step is the actual,
uncorrected airflow.

1. Wait for the maximum airflow value

to stabilize.

2. With a flow hood, measure the actual

airflow.

3. Press the button to advance to the

entry display. SMAX stops flashing.

4. Press the or buttons to enter the

measured airflow.

5. Press the button to save the

measured airflow. The display
advances to SMIN.

The airflow balancing procedure (Continued)

Procedure

Steps

STE display

Set

Point

PRI

SEC

Set

Point

Set

Point

SMAX

OO