Commissioning functions
Balancing airflow

28

Measure and enter
the actual
maximum primary
airflow

The display begins flashing PMAX
and also displays the actual airflow
at the bottom.

Note:

The airflow will attempt to stabilize

on the highest value for either the cooling
or heating maximum airflow even if only
one mode is operational.

Note:

The airflow displayed by the

STE-8000 in this step is the actual,
uncorrected airflow.

1. Wait for the maximum airflow value

to stabilize.

2. With a flow hood, measure the actual

airflow.

3. Press the button to advance to the

entry display. PMAX stops flashing.

4. Press the or buttons to enter the

measured airflow.

5. Press the button to save the

measured airflow. The display
changes to PMIN.

Measure and enter
the actual
minimum primary
airflow

The display begins flashing PMIN
and also displays the actual airflow
at the bottom.

Note:

The airflow will attempt to stabilize

on the lowest value for either the cooling
or heating minimum airflow even if only
one mode is operational.

Note:

The airflow displayed by the

STE-8000 in this step is the actual,
uncorrected airflow.

1. Wait for the minimum airflow value

to stabilize.

2. With a flow hood, measure the actual

airflow.

3. Press the button to advance to the

entry display. PMIN stops flashing.

4. Press the or buttons to enter the

measured airflow.

5. Press the button to save the

measured airflow. The display
advances to PRI.

The airflow balancing procedure (Continued)

Procedure

Steps

STE display

Set

Point

Set

Point

PMAX

OO

Set

Point

Set

Point

PMIN

OO